Input Ranges
Models with Thermocouple Inputs
Default setting: 0
Applicable standards (K, J, T, R, S): JIS C1602-1995 and IEC 60584-1
Platinum Resistance Thermometer Input
Default setting: 8
Applicable standards (Pt100): JIS C1604-1997 and IEC 60751
Alarm Types
Select alarm types out of the 11 alarm types listed in the following table.
Note: 1. The default is 2.
2. Alarms with a Standby Sequence
The alarm is blocked until the first safe-state is reached.
Unwanted alarm during start-up are prevented.
Example: Deviation Lower Limit Standby Sequence ON
The standby sequence is cleared when the alarm OFF condition has
been met.
The standby sequence is started again when any of the following
conditions is met.
Operation is started (power is turned ON or operation is switched
from stop to run).
The alarm value is changed.
The temperature input offset is changed.
The set point is changed.
Model
(temperature input)
Set value Input type
Range
C F
TC input
0
K
200 to 1,300 300 to 2,300
1 20.0 to 500.0 0.0 to 900.0
2
J
100 to 850 100 to 1500
3 20.0 to 400.0 0.0 to 750.0
4
T
200 to 400 300 to 700
5 199.9 to 400.0 199.9 to 700.0
6 R 0 to 1,700 0 to 3,000
7 S 0 to 1,700 0 to 3,000
Model
(temperature input)
Set value Input type
Range
C F
Pt input
8
Pt100
200 to 850 300 to 1500
9 199.9 to 500.0 199.9 to 900.0
Setting Alarm type Positive alarm value (X) Negative alarm value (X) Deviation alarm/absolute value alarm
0 No alarm Output OFF
1 Upper/lower limit Always ON Deviation alarm
2 Upper limit Deviation alarm
3 Lower limit Deviation alarm
4 Upper/lower range Always OFF Deviation alarm
5
(See note 2.)
Upper/lower limit standby
sequence ON
Always OFF Deviation alarm
6
(See note 2.)
Upper limit standby sequence
ON
Deviation alarm
7
(See note 2.)
Lower limit standby sequence
ON
Deviation alarm
8 Absolute value upper limit Absolute value alarm
9 Absolute value lower limit Absolute value alarm
10
(See note 2.)
Absolute value upper limit
standby sequence ON
Absolute value alarm
11
(See note 2.)
Absolute value lower limit
standby sequence ON
Absolute value alarm
12 Do not set.
ON
OFF
SP
XX
SP
X
ON
OFF
SP
X
ON
OFF
SP
X
ON
OFF
SP
X
ON
OFF
SP
XX
ON
OFF
SP
XX
ON
OFF
SP
X
ON
OFF
SP
X
ON
OFF
SP
X
ON
OFF
SP
X
ON
OFF
0
X
ON
OFF
0
X
ON
OFF
0
X
ON
OFF
0
X
ON
OFF
0
X
ON
OFF
0
X
ON
OFF
0
X
ON
OFF
0
X
ON
OFF
Alarm hysteresis
(always 0.2 °C/°F)
Alarm without standby sequence
Time
Process value
Alarm with standby sequence
Alarm value
Standby sequence cleared
H09E-EN-01+E5CB+Datasheet.fm Seite 3 Freitag, 21. Januar 2011 12:03 12