Amplifier Unit
Installation
Operation after Turning Power ON
The Amplifier Unit is ready to operate within 200 ms after the power supply is
turned ON. If the Sensor and load are connected to power supplies separately, be
sure to turn ON the power supply to the Sensor first.
Mounting
Connecting and Disconnecting Connectors
Mounting Connectors
1. Insert the Master or Slave Connector into the Amplifier Unit until it clicks into
place.
2. Attach the protector seals (provided as accessories) to the sides of master and
slave connectors that are not connected.
Note: Attach the seals to the sides with grooves
Removing Connectors
1. Slide the slave Amplifier Unit(s) for which the Connector is to be removed away
from the rest of the group.
2. After the Amplifier Unit(s) has been separated, press down on the lever on the
Connector and remove it. (Do not attempt to remove Connectors without sep-
arating them from other Amplifier Units first.)
Joining and Removing Amplifier Units
Joining Amplifier Units
1. Mount the Amplifier Units one at a time onto the DIN track.
2. Slide the Amplifier Units together, line up the clips, and press the Amplifier
Units together until they click into place.
Separating Amplifier Units
Slide Amplifier Units away from each other, and remove from the DIN track one at
a time. (Do not attempt to remove Amplifier Units from the DIN track without sep-
arating them first.)
Note: - The specifications for ambient temperature will vary according to the number of
Amplifier Units used together. For details, refer to Ratings/Characteristics.
- Always turn OFF the power supply before joining or separating Amplifier Units.
Mounting the End Plate (PFP-M)
An End Plate should be used if there is a possibility of the Amplifier Unit moving,
e.g., due to vibration. If a Mobile Console is going to be mounted, connect the End
Plate in the direction shown in the following diagram.
Mounting the Mobile Console Head
Leave a gap of at least 20 mm between the nearest Amplifier Unit and the Mobile
Console head.
Fiber Connection
The E3X Amplifier Unit has a lock button for easy connection of the Fiber Unit.
Connect or disconnect the fibers using the following procedures:
1. Connection
Open the protective cover, insert the fibers according to the fiber insertion marks
on the side of the Amplifier Unit, and lower the lock button.
Fibers with E39-F9 Attachment
Insert
Seal
Seal
Press down
Remove
Lever
Click into place
End Plate
20 mm
Lock button
Fiber
Fiber insertion
mark
Locked
Unlocked
Insertion position
Protective cover
9 mm
Fiber Unit
9 mm
13 mm