E2E2-X
Y
AC 2-wire Models
Part number E2E2-X2Y
-
US
E2E2-X5M
-U
S
E2E2-X5Y
-US
E2E2-X10MY
-
US
E2E2-X10
-U
S
E2E2-X18MY
-
US
Size M12 M18 M30
Type Shielded Unshielded Shielded Unshielded Shielded Unshielded
Sensing distance 2 mm (0.08 in)
±10%
5 mm (0.20 in)
±10%
5 mm (0.20
in) ±10%
10 mm (0.39 in)
±10%
10 mm (0.39
in) ±10%
18 mm (0.71 in)
±10%
Supply voltage (operating
voltage range) (see note 1)
24 to 240 VAC, 50/60 Hz (20 to 264 VAC)
Leakage current 1.7 mA max.
Sensing object Magnetic metals
Setting distance 0to1.6mm
(0 to 0.06 in)
0to4.0mm
(0 to 0.16 in)
0to4.0mm
(0 to 0.16 in)
0to8.0mm
(0 to 0.31 in)
0to8.0mm
(0 to 0.31 in)
0 to 14.0 mm
(0 to 0.55 in)
Standard object (mild steel) 12 x 12 x
1 mm (0.47 x
0.47 x 0.04 in)
15 x 15 x 1 mm
(0.59 x 0.59 x
0.04 in)
18 x 18 x
1 mm (0.71 x
0.71 x 0.04
in)
30x30x1mm
(1.18 x 1.18 x
0.04 in)
30 x 30 x
1 mm (1.18 x
1.18 x 0.04 in)
54 x 54 x 1 mm
(2.13 x 2.13 x
0.04 in)
Differential travel 10% max. of sensing distance
Response frequency 25 Hz
Operation (with sensing
object approaching)
Y1 models: Load ON
Y2 models: Load OFF
Control output (switching
capacity)
5 to 200 mA 5 to 300 mA (see note 2)
Indicator Operation indicator (red LED)
Ambient temperature Operating: --40°Cto85°Cwithnoicing(--40°F to 185°F)
Ambient humidity Operating: 35% to 95%
Temperature influence ±15% max. of sensing distance at 23°C in temperature range of --40°Cto85°C(--40°F to 185°F)
±10% max. of sensing distance at 23°C in temperature range of --25°Cto70°C(--13°F to 158°F)
Voltage influence ±1% max. of sensing distance in rated voltage range ±15%
Residual voltage Refer to
Engineering Data
Insulation resistance 50 MΩ min. (at 500 VDC) between current carry parts and case
Dielectric strength 4,000 VAC for 1 min between current carry parts and case
Vibration resistance Destruction: 10 to 55 Hz, 1.5-mm double amplitude for 10 times each in X, Y, and Z directions
Shock resistance Destruction: 1,000 m/s
2
(approx. 100G) for 10 times each in X, Y, and Z directions
Enclosure
IEC IP67
c
o
s
u
e
rating
NEMA 1, 4, 6, 12, 13
Weight 65 g 150 g 220 g
Approvals
UL Recognized, File Number E76675
o
a
s
CSA Certified, File Number LR45951
Material
Body Brass
a
e
a
Sensing face PBT
Note: 1. When using an M18 or M30 size E2E2 at an ambient temperature between 70°C and 85°C, make sure the E2E2 has a control
output of 200 mA maximum.
2. When supplying 24 VAC to any of the above models, make sure that the operating ambient temperature range is --25°Cto85°C
(--13°F to 185°F).
E2E2 E2E2