Datasheet
E2E2-X
Y
-M4 AC 2-wire Model
Applicable Models Pin Arrangement
E2E2-X
Y
-M4
Load
32
AC
MOUNTING
Do not tighten the nut with excessive force. A washer must be used
with the nut.
Shielded Model Unshielded Model
Part B Part A
Part B Part A
Note: The table below shows the tightening torques for part A and
part B nuts. In the previous examples, the nut is on the sen-
sor head side (part B) and hence the tightening torque for
part B applies. If this nut is inpart A, thetightening torque for
part A applies instead.
Type
Torque
M12 30 N
m (310 kgf
cm)
M18 70 N
m (710 kgf
cm)
M30 180 N
m (1,800 kgf
cm)
Effects of Surrounding Metal
When mounting the E2E2 within a metal panel, ensure that the
clearances given in the table below are maintained. Failure to main-
tain these distances may cause deterioration in the performance of
the sensor.
ddia.
Type Item M12 M18 M30
E2E2-X
D
Shielded
0mm 0mm 0mm
DC 2-wire
d 12 mm 18 mm 30 mm
D 0mm 0mm 0mm
m 8mm 20 mm 40 mm
n 18 mm 27 mm 45 mm
Unshielded
15 mm 22 mm 30 mm
U
s
e
d
e
d
d 40 mm 70 mm 90 mm
D 15 mm 22 mm 30 mm
m 20 mm 40 mm 70 mm
n 40 mm 70 mm 90 mm
E2E2-X
B
Shielded
0mm 0mm 0mm
E2E2-X
C
D
C
3
w
i
r
e
d 12 mm 18 mm 30 mm
DC 3-wire
E
E
X
Y
D 0mm 0mm 0mm
E2E2-X
Y
A
C
2
w
i
r
e
m 8mm 20 mm 40 mm
AC 2-wire
n 18 mm 27 mm 45 mm
Unshielded
15 mm 22 mm 30 mm
d 40 mm 55 mm 90 mm
D 15 mm 22 mm 30 mm
m 20 mm 40 mm 70 mm
n 36 mm 54 mm 90 mm
E2E2 E2E2