Datasheet
E2E
16
E2E-X@E@/F@ DC 3-Wire Models
*1. The response frequency is an average value. Measurement conditions are as follows: standard sensing object, a distance of twice the standard sensing object, and
a set distance of half the sensing distance.
*2. When using an M8 Model at an ambient temperature between 70 and 85°C, supply 10 to 30 VDC to the Sensor and make sure that the Sensor has a control output
of 100 mA maximum.
*3. For the information on UL-certified connector models, refer to your OMRON website.
Size M8 M12 M18 M30
Shielded Shielded Unshielded Shielded Unshielded Shielded Unshielded Shielded Unshielded
Item Model
E2E
-X1R5E@/F@
E2E
-X2ME@/F@
E2E
-X2E@/F@
E2E
-X5ME@/F@
E2E
-X5E@/F@
E2E
-X10ME@/F@
E2E-X10E@/
F@
E2E
-X18ME@/F@
Sensing distance 1.5 mm ±10% 2 mm ±10% 5 mm ±10% 10 mm ±10% 18 mm ±10%
Set distance 0 to 1.2 mm 0 to 1.6 mm 0 to 4 mm 0 to 8 mm 0 to 14 mm
Differential travel 10% max. of sensing distance
Detectable object Ferrous metal (The sensing distance decreases with non-ferrous metal. Refer to Engineering Data on page 18.)
Standard sensing
object
Iron,
8 × 8 × 1mm
Iron, 12 × 12 × 1 mm
Iron,
15 ×15 × 1mm
Iron,
18 × 18 × 1 mm
Iron, 30 × 30 × 1 mm
Iron,
54 × 54 × 1 mm
Response frequency
*1
2 kHz 0.8 kHz 1.5 kHz 0.4 kHz 0.6 kHz 0.2 kHz 0.4 kHz 0.1 kHz
Power supply voltage
(operating voltage
range)
*2
12 to 24 VDC, ripple(p-p): 10% max. (10 to 30 VDC)
Connector Models Used as UL-certified Models: 12 to 24 VDC, ripple (p-p): 10% max. (The operating voltage range is also the same.) *3
Current consumption 13 mA max.
Control
output
Load
current *2
200 mA max.
Residual
voltage
2 V max. (Load current: 200 mA, Cable length: 2 m)
Indicators Operation indicator (red)
Operation mode
(with sensing object
approaching)
E1/F1 Models: NO
E2/F2 Models: NC
Refer to the timing charts under /O Circuit Diagrams on page 21 for details.
Protection circuits Load short-circuit protection, Surge suppressor, Reverse polarity protection
Ambient
temperature range *2
Operating/Storage: −40 to 85°C (with no icing or condensation)
Ambient humidity
range
Operating/Storage: 35% to 95% (with no condensation)
Temperature
influence
±15% max. of sensing distance at 23°C in the temperature range of −40 to 85°C
±10% max. of sensing distance at 23°C in the temperature range of −25 to 70°C
Voltage influence ±1% max. of sensing distance at rated voltage in the rated voltage ±15% range
Insulation resistance 50 MΩ min. (at 500 VDC) between current-carrying parts and case
Dielectric strength 1,000 VAC, 50/60 Hz for 1 minute between current carry parts and case
Vibration resistance Destruction: 10 to 55 Hz, 1.5-mm double amplitude for 2 hours each in X, Y, and Z directions
Shock resistance
Destruction: 500 m/s
2
10 times each in X, Y, and
Z directions
Destruction: 1,000 m/s
2
10 times each in X, Y, and Z directions
Degree of protection
Pre-wired Models : IEC 60529 IP67, in-house standards: oil-resistant
Connector Models : IEC 60529 IP67
Connection method Pre-wired Models (Standard cable length: 2 m) and Connector Models
Weight
(packed
state)
Pre-
wired
Models
Approx. 65 g Approx. 75 g Approx. 150 g Approx. 195 g
Connec-
tor
Models
Approx. 15 g Approx. 25 g Approx. 40 g Approx. 90 g
Materials
Case Stainless steel (SUS303) Nickel-plated brass
Sensing
surface
PBT
Clamp-
ing nuts
Nickel-plated brass
Toothed
washer
Zinc-plated iron
Accessories Instruction manual