Datasheet

D4SL-N / D4SL-NSK10-LK@
25
Wiring Precautions for D4SL-N@@@@-@@
Do not wire the Switch while power is being supplied. Doing so may
result in electric shock.
Do not let particles, such as small pieces of lead wire, enter the
switch body when wiring.
Do not directly wire the stranded wire to the terminal block.
When connecting to the terminals via insulating tube and bar
terminals, arrange the bar terminals so that they do not rise up onto
the case or the cover.
Applicable lead wire size: AWG22 to AWG18 (0.3 to 0.75 mm
2
).
Use lead wires of an appropriate length. Not doing so may result in
excess length causing the cover to rise and not fit properly.
Remove the terminal block board out of the unit to perform wiring.
Be sure to insert the connector properly.
Do not pull on the lead wires with excessive force. Doing so may
disconnect them.
Recommended Crimp Terminals
Wiring Precautions for D4SL-N@@@@-@@N
Do not wire the Switch while power is being supplied. Doing so may
result in electric shock.
Do not let particles, such as small pieces of lead wire, enter the
switch body when wiring.
Applicable lead wire size: AWG24 to AWG22 (0.2 to 0.3 mm
2
).
Do not apply a current of 2 A or more when using AWG24.
Use lead wires of an appropriate length. Not doing so may result in
excess length causing the cover to rise and not fit properly.
Do not pull on the lead wires with excessive force. Doing so may
disconnect them.
Do not forcibly insert the wired socket at the cable side into the
connector or D4SL-N’s conduit outlet. Doing so may cause cable
break.
Be sure to insert the cable into the connector or D4SL’s conduit
outlet before performing wiring to the socket, or insert the cable
into the connector or conduit outlet from the opposite side of the
socket.
Applicable socket for cable side
Processing the Conduit Outlet
Use a recommended cable gland and tighten it with the appropriate
tightening torque. The case may be damaged if an excessive
tightening torque is applied.
Use a cable conforming to the diameter of the cable gland to be
used.
For the 1/2-14NPT conduit, mount a provided conversion adapter
and wrap the seal tape around it to use the cable gland.
Cable Gland
Use a commercially available cable gland.
Use a cable gland with a screw section not exceeding 9 mm to
ensure wiring properties.
Manufacturer Model Applicable wire lead
PHOENIX
CONTACT
AI0.34-8 TQ AWG22
AI0.5-8 WH AWG20
AI0.75-8 GY AWG18
30
±3
mm
40
±3
mm
1 3 5 7 9
2 4 6 8
10
1
3
5
7
9
2
4
6
8
10
L1
L2
L1: 14 mm max.
L2: 8 mm max.
1 2
10
30
±3
mm
45610321
Manufacturer Name Model
J.S.T. Mfg Co.
Housing XHP-10
Contact
(applicable wire lead:
AWG24 to AWG22)
SXH-001T-P0.6