Application Example
Note: The above PL is only the evaluation result of the example. The PL must be evaluated in an actual application by the customer after confirming
the usage conditions.
Application Overview
After the opening of the guard is permitted by turning ON of the lock release enable signal, the guard is opened by operating the lock release
switch S4.
The guard status is monitored by the Safety Limit Switch S1 and Guard Lock Safety-door Switch S2, and a state in which the power supply to
the motor M is turned OFF must be maintained while the guard is open.
When the guard is closed, lock status is ensured, and the reset switch S3 is pressed, the power supply to the motor M is permitted.
Highest achievable PL/
safety category
Model Stop category Reset
PLe/4 equivalent
Guard Lock Safety-door Switch D4SL-N@E@A-@ (Mechanical Lock Type)
Safety Limit Switch D4N/D4F/D4B-N
Safety Relay Unit G9SE-201 (24 VAC/VDC)
0 Manual
A1 T11 T31 T32 T33 13 23T12
A2 T21
X1
14
24
T22
Auxiliary
output
Power
supply
circuit
Safety
Input1
Safety
Input2
Reset/
Feedback
Input
Safety
Output
(Instant
aneous)
64
63
22
21
34
33
S3
KM1
KM2
KM1
KM2
M
S4
Lock release
enable signal
Guard
24 V
41
42
S2
S1
12
11
Condition monitoring of
Safety-door Switch
Feedback loop
PLC etc. KM1 KM2
10
9
1 2 3 4 5 6 7 8
open
KM1 and KM2 (NO)
Motor M rotation
Reset switch S3
Lock release switch S4
Lock release enable signal
Safety Limit Switch S1
Guard Lock Safety-door Switch S2
Door open/closed monitor contact
Guard Lock Safety-door Switch S2
Lock monitor contact
Guard closesGuard opens
Timing Chart
Guard can be opened
S1: Safety Limit Switch with direct opening mechanism
S2: Guard Lock Safety-door Switch D4SL-N@E@A-@
S3: Reset switch
S4: Lock release switch
KM1 and KM2: Magnetic contactor
M: Motor
Note: The lock release enable signal must be configured so that
it should turn ON after dangerous movement is stopped
and safety is ensured for the door to open.