Datasheet
D4SL-N / D4SL-NSK10-LK@
25
Wiring Precautions for D4SL-N@@@@-@@
• Do not wire the Switch while power is being supplied. Doing so may
result in electric shock.
• Do not let particles, such as small pieces of lead wire, enter the
switch body when wiring.
• Do not directly wire the stranded wire to the terminal block.
• When connecting to the terminals via insulating tube and bar
terminals, arrange the bar terminals so that they do not rise up onto
the case or the cover.
• Applicable lead wire size: AWG22 to AWG18 (0.3 to 0.75 mm
2
).
• Use lead wires of an appropriate length. Not doing so may result in
excess length causing the cover to rise and not fit properly.
• Remove the terminal block board out of the unit to perform wiring.
Be sure to insert the connector properly.
• Do not pull on the lead wires with excessive force. Doing so may
disconnect them.
Recommended Crimp Terminals
Wiring Precautions for D4SL-N@@@@-@@N
• Do not wire the Switch while power is being supplied. Doing so may
result in electric shock.
• Do not let particles, such as small pieces of lead wire, enter the
switch body when wiring.
• Applicable lead wire size: AWG24 to AWG22 (0.2 to 0.3 mm
2
).
Do not apply a current of 2 A or more when using AWG24.
• Use lead wires of an appropriate length. Not doing so may result in
excess length causing the cover to rise and not fit properly.
• Do not pull on the lead wires with excessive force. Doing so may
disconnect them.
• Do not forcibly insert the wired socket at the cable side into the
connector or D4SL-N’s conduit opening. Doing so may cause
cable break.
Be sure to insert the cable into the connector or D4SL’s conduit
opening before performing wiring to the socket, or insert the cable
into the connector or conduit opening from the opposite side of the
socket.
Applicable socket for cable side
Processing the Conduit Opening
• Connect a recommended connector to the opening of the conduit
and tighten the connector to the proper torque. The case may be
damaged if excessive tightening torque is applied.
• Use the cable with the connector-specified outside diameter.
• For the 1/2-14NPT conduit, mount a provided conversion adapter
to use the connector above.
Recommended Connectors
• Use a connector with a screw section not exceeding 9 mm.
Otherwise the screws will protrude into the case interior.
The connectors given in the following table have connectors with
screw sections not exceeding 9 mm.
Use the following connectors to ensure conformance to IP67.
• Use LAPP connectors together with Seal Packing (JPK-16 for G1/
2, or GPM20 for M20), and tighten to the applicable torque. Seal
Packing is sold separately.
• LAPP is a German manufacturer.
• Ace Service Co. is a Japanese manufacturer.
Manufacturer Model Applicable wire lead
PHOENIX
CONTACT
AI0.34-8 TQ AWG22
AI0.5-8 WH AWG20
AI0.75-8 GY AWG18
Manufacturer Name Model
J.S.T. Mfg Co.
Housing XHP-10
Contact
(applicable wire lead:
AWG24 to AWG22)
SXH-001T-P0.6
30
±3
mm
40
±3
mm
1 3 5 7 9
2 4 6 8
10
1
3
5
7
9
2
4
6
8
10
L1
L2
L1: 14 mm max.
L2: 8 mm max.
1 2
10
30
±3
mm
45610321
Size Manufacturer Model
Applicable cable
diameter
Remarks
G1/2
LAPP
ST-PF1/2
5380-1002
6.0 to 12.0 mm
Ace Service Co. LS-2G 6.0 to 11.0 mm Short type
M20 LAPP
ST-M20×1.5
5311-1020
7.0 to 13.0 mm
1/2-
14NPT
LAPP
ST-NPT1/2
5301-6030
6.0 to 12.0 mm