Datasheet

D4NL
7
Connections
Internal Circuit Diagram
Indicator
Solenoid
Circuit Connection Example
Connection Example for D4NL-@F@@-B
Terminals 12 and 41 are connected internally. When connecting
inputs to safety circuits, use terminals 11 and 42. (GS-ET-19).
Connect terminals 21 and 22 and terminals 51 and 52 in series
when using as safety-circuit inputs (redundancy circuit for
terminals 11 and 12 and terminals 41 and 42 below). Connect the
terminals individually when using as auxiliary-circuit inputs (e.g.,
terminals 21 and 22 for safety-door open/closed monitoring and
terminals 51 and 52 for monitoring the lock status).
In the following connection example, terminals 21 and 22 and
terminals 51 and 52 are used as auxiliary-circuit inputs.
Direct opening contacts used as safety-circuit inputs are indicated
with the mark. Terminals 11 and 42, and terminals 21 and 22
have direct opening contacts.
Connect the indicators in parallel to the auxiliary circuits or
terminals E1 and E2 (D4NL-@@@A-B, -@@@G-B, -@@@B-B, and
-@@@H-B only).
Connecting to contacts with direct opening mechanisms may result
in short-circuit current flowing if the indicator is destroyed, possibly
resulting in incorrect equipment operation.
Do not switch circuits for two or more standard loads at the same
time. Doing so may adversely affect insulation performance.
DC solenoids have polarity. Confirm terminal polarity before wiring.
D
R
R
LED
Z
10 to 115 VAC/VDC
Constant-current diode
E1 (+)
E2 ()
110 VAC/230 VAC
42
11
21
33
E1 (+)
O1 O2
12 41
5
1
52
22
34
E2 ()
Indicator
(Orange)
Safety
circuit
Auxiliary
circuit
Auxiliary
circuit
Auxiliary
circuit