G-272 Safety Sensors / Components
Direct Opening Mechanism
1NC/1NO Contact (Slow-action)
2NC Contact (Slow-action)
Contact spring
Return spring
Fixed contact (NC)
Fixed contact (NO)
Plunger
Movable contacts
Only the NC contact side has a direct opening
mechanism.
When metal deposition occurs, the contacts are
separated from each other by the plunger being
pushed in.
(Conforms to EN60947-5-1 Direct Opening Operation.)
Contact spring
Return spring
Fixed contact (NC)
Plunger
Movable contact
Both NC contacts have a direct opening mechanism.
When metal deposition occurs, the contacts are
separated from each other by the plunger being
pushed in.
(Conforms to EN60947-5-1 Direct Opening Operation.)