Datasheet
Small Sealed Switch D4E-@NF-33
Limit
Switches
Specifications
■ Approved Standards
■ Approved Standard Ratings
UL, CSA
A300
TÜV (EN60947-5-1)
Note: 1. @: Actuator variation of item II
2. AC-14 0.5 A/125 VAC means as follows:
Applicable category: AC-14
Rated operating current (I
e
): 0.5 A
Rated operating voltage (U
e
): 125 VAC
Agency Standard File No.
UL UL508 E76675
CSA CSA C22.2 No. 14 LR45746
TÜV Rheinland EN60947-5-1 R9551015
Voltage Carry current Current Volt-amperes
Make Break Make Break
120 V 10 A 60 A 6 A 7,200 VA 720 VA
240 V 30 A 3 A
Model Applicable category and ratings Thermal
current (I
the
)
Indicator
I II III IV
1 @ 00 AC-14 0.5 A/125 VAC 5 A ---
1 @ 10 DC-12 0.5 A/30 VDC 5 A ---
1 @ 20, 21, 22 AC-15 2A/250 VAC
DC-12 2A/48 VDC
5 A ---
1 @ 23, 24 L AC-15 2A/250 VAC 5 A Neon lamp
1 @ 23, 24 L1 DC-12 2A/12 VDC 5 A LED
1 @ 23, 24 L2 DC-12 2A/24 VDC 5 A LED
1 @ 23, 24 L3 DC-12 2A/48 VDC 5 A LED
2 @ 00 AC-14 0.1A/125 VAC 0.5 A ---
2 @ 10 DC-12 0.1A/30 VDC 0.5 A ---
2 @ 20, 21, 22 AC-14 0.1A/125 VAC
DC-12 0.1A/48 VDC
0.5 A ---
2 @ 23, 24 L AC-14 0.1A/125 VAC 0.5 A Neon lamp
2 @ 23, 24 L1 DC-12 0.1A/12 VDC 0.5 A LED
2 @ 23, 24 L2 DC-12 0.1A/24 VDC 0.5 A LED
2 @ 23, 24 L3 DC-12 0.1A/48 VDC 0.5 A LED
I II III IV
D4E-
1 G 23 L N