Datasheet

15
D4BL
Processing and Connecting Cable/
Conduit
The following procedures are recommended for mounting and
wiring the indicator unit securely.
To ensure IP67, use OMRON’s SC-@M and Nippon Flex’s
ABS-08Pg13.5 and ABS-12 Pg13.5 Connectors.
Recommended cable: UL2464-type cable that is AWG20 to
AWG18 (0.5 to 1.0 mm
2
) in size and has seven conductors
Connect the indicator unit after connecting the seven-conductor
cable.
Properly attach and securely tighten the provided conduit cap to
the unused conduit opening to the suitable tightening torque when
wiring the D4BL.
Cable Connection Example
1. Connect the wires to the terminals in the order shown below for
wiring efficiency.
Tighten each wired terminal clockwise to a torque of 0.59 to
0.78 N·m.
Twist the wire two or three times and make sure that no bare wire
exists outside the terminal when tightening the terminal.
2. The insulation sheath of the seven-conductor cable must come into
contact with the wall of the conduit mouth, side A or side B.
Others
Do not touch the solenoid because the solenoid radiates heat while
power is being supplied.
Terminal no. Lp (mm) Lv (mm) a (mm)
E
1 30±280±2
8±1
E
2 35±275±2
31 45±260±2
12 55±250±2
23 (21) 65±245±2
24 (22) 70±235±2
90±250±2
Insulation sheath edge