Datasheet

D4BL
10
Circuit Connection Example
Terminals 11 and 32 are connected internally and so connect terminals 12 and 31 for safety-circuit input. (GS-ET-19).
When using indicators, connect them to the auxiliary circuit side (monitor circuit) or in parallel between E1 and E2 as shown below.
Do not connect the indicators in parallel with the direct opening contact. If the indicators are broken, a short-circuit current may flow, causing
equipment to malfunction.
The 24 VDC solenoid terminals have polarity. Confirm the polarity before wiring.
1112 31
E2 ()
E1 (+)
32
23 24
1112 31
E2 ()
E1 (+)
32
23 24
1112 31
E2 ()
E1 (+)
32
21 22
1112 31
E2 ()
E1 (+)
32
2221
1. Orange: Lights when the solenoid turns ON.
Green: Lights when the door opens.
(Power supply side)
Solenoid
LED (orange)
LED (green)
Auxiliary circuit
(monitor circuit)
Safety circuit
2. Orange: Lights when the solenoid turns ON.
Green: Lights when power turns ON.
(Power supply side)
Solenoid
LED (orange)
LED (green)
Auxiliary circuit
(monitor circuit)
Safety circuit
3. Orange: Lights when the solenoid turns ON.
Green: Lights when door closes.
(Power supply side)
Solenoid
LED (orange)
LED (green)
Auxiliary circuit
(monitor circuit)
Safety circuit
4. Orange: Lights when the solenoid turns ON.
Green: Lights when power turns ON.
(Power supply side)
Solenoid
LED (orange)
LED (green)
Auxiliary circuit
(monitor circuit)
Safety circuit