Datasheet

G-189F3SL
D4BL
Connections
Indicator Unit
Dimensions
Internal Circuit
Circuit Connection Example
Do not connect the indicators to the safety contact terminals (11-
12-31-32) or the safety circuit side.
When using indicators, connect them to the auxiliary circuit side
(monitor circuit) or the solenoid input terminals as shown below.
The indicators can be used to confirm the open/closed status of the
door, the ON/OFF status of the power supply, and the ON/OFF sta-
tus of the solenoid.
Do not connect the indicators in parallel with the direct opening
contact. If the indicators are broken, a short-circuit current may
flow, causing equipment to malfunction.
The 24-VDC solenoid terminals have polarity. Confirm the polarity
before wiring.
Be sure to use a special pushbutton switch to stop and start
machinery and release locks.
(16)
(16)
(7)
(35) 26.2
(61.2)
0.3
5.6
26.8
53.2 57.2
2 10.6
(12.6)
Two, 7 dia.
Four terminal plates
Two LED indicators
R
Z
D
R
LED
10 to 115 VAC/DC
Constant-current diode
1211 32
E2 ()
E1 (+)
31
23 24
1211 32
E2 ()
E1 (+)
31
23 24
1211 32
E2 ()
E1 (+)
31
21 22
1211 32
E2 ()
E1 (+)
31
21 22
1. Orange: Lights when the solenoid turns ON.
Green: Lights when the door opens.
(Power supply side)
Solenoid
LED (orange)
LED (green)
Auxiliary circuit
(monitor circuit)
Safety circuit
(Ground side)
2. Orange: Lights when the solenoid turns ON.
Green: Lights when power turns ON.
(Power supply side)
Solenoid
LED (orange)
LED (green)
Auxiliary circuit
(monitor circuit)
Safety circuit
(Ground side)
3. Orange: Lights when the solenoid turns ON.
Green: Lights when door closes.
(Power supply side)
Solenoid
LED (orange)
LED (green)
Auxiliary circuit
(monitor circuit)
Safety circuit (Ground side)
4. Orange: Lights when the solenoid turns ON.
Green: Lights when power turns ON.
(Power supply side)
Solenoid
LED (orange)
LED (green)
Auxiliary circuit
(monitor circuit)
Safety circuit (Ground side)