Datasheet

G-187F3SL
D4BL
Approved Standard Ratings
TÜV (EN60947-5-1)
Use a 10-A fuse type gI or gG that conforms to IEC269 as a short-circuit protection device.
UL/CSA (UL508, CSA C22.2 No. 14)
A300
Note: The UL/CSA approved rating for products with indicators (-A) is 6 A/115 VAC.
Characteristics
Note: 1. The above values are initial values.
2. Although the switch box is protected from dust, oil or water penetration, do not use the D4BL in places where dust, oil, water, or chemicals
may penetrate through the key hole on the head, otherwise Switch damage or malfunctioning may occur.
3. The durability is for an ambient temperature of 5°C to 35°C and an ambient humidity of 40% to 70%.
Item Standard model Indicator model
Utilization category AC-15 AC-15
Rated operating current (Ie) 3 A 6 A
Rated operating voltage (Ue) 250 V 115 V
Rated voltage Carry current
Current Volt-amperes
Make Break Make Break
120 VAC
10 A
60 A 6 A
7,200 VA 720 VA
240 VAC
30 A 3 A
Degree of protection IP67 (See note 2.)
Durability (See note 3.)
Mechanical:1,000,000 operations min.
Electrical:500,000 operations min. (10-A resistive load at 250 VAC)
Operating speed 0.05 to 0.5 m/s
Operating frequency 30 operations/min max.
Rated frequency 50/60 Hz
Operating characteristics
Direct opening force:19.61 N min. (EN60947-5-1)
Direct opening travel:20 mm min. (EN60947-5-1)
All stroke:23 mm min.
Holding force 700 N min. (GS-ET-19)
Insulation resistance 100 M min. (at 500 VDC)
Rated insulation voltage (U
i
) 300 V (EN60947-5-1)
Conventional enclosed thermal current
(I
the
)
10 A (EN60947-5-1)
Dielectric strength (U
imp
)
Impulse dielectric strength (U
imp
) 4 kV (EN60947-5-1) between terminals of different polarity, be-
tween each terminal and ground, and between each terminal and non-current-carrying metal
part;
2.5 kV between solenoid and ground (EN60947-5-1)
Conditional short-circuit current 100 V (EN60947-5-1)
Pollution degree
(operating environment)
3 (EN60947-5-1)
Protection against electric shock Class I (with ground terminal)
Switching overvoltage 1,500 V max. (EN60947-5-1)
Contact resistance 50 m max. (initial value)
Vibration resistance Malfunction: 10 to 55 Hz, 0.35-mm single amplitude
Shock resistance
Destruction:1,000 m/s
2
min. (IEC68-2-27)
Malfunction:300 m/s
2
min. (IEC68-2-27)
Ambient temperature Operating:–10°C to 55°C (with no icing)
Ambient humidity Operating:95% max.
Weight Approx. 800 g
F502-EN2-04.book Seite 187 Dienstag, 26. Juli 2005 5:48 17