Datasheet

G9SX-NS
15
Characteristics
*1. When two or more Units are connected by logical AND, the operating time and response time are the sum total of the operating times and
response times, respectively, of all the Units connected by logical AND.
The operating time/response time of the Non-contact Door Switch are included of the time with the D40A/D40Z.
*2. Represents the operating time when the safety input turns ON with all other conditions set.
*3. Represents the operating time when the logical AND input and the Non-contact Door Switch input turn ON with all other conditions set.
*4. This does not include the operating time or response time of G9SX-NS@ that are connected.
*5. This does not include the operating time or response time of internal relays in the G9SX-EX-@.
*6. The failure detection time for 24 V short-circuit failure on the input to Non-contact Door Switches is 35 ms max.
If using the Switch for an application other than as a Door Switch, calculate the safe distance using a failure detection time of 35 ms.
Item Model G9SX-NS202-@ G9SX-NSA222-T03-@ G9SX-EX-@
Over-voltage category
(IEC/EN 60664-1)
II
II (Relay outputs 13 to 43
and 14 to 44: III)
Operating time (OFF to ON state) *1
Logical AND connection input:
100 ms max.
D40A connected: 100 ms max.
D40Z connected: 200 ms max.
Safety input: 50 ms max. *2
Logical AND connection input:
100 ms max. *3
D40A connected: 100 ms max. *3
D40Z connected: 200 ms max. *3
30 ms max. *4
Response time (ON to OFF state) *1
15 ms max. (Logical AND
connection input: OFF)
Logical AND connection input:
15 ms max.
D40A connected: 20 ms max. *6
D40Z connected: 45 ms max.
15 ms max. (Logical AND
connection input: OFF)
Safety input: 15 ms max.
Logical AND connection input:
15 ms max.
D40A connected: 20 ms max. *6
D40Z connected: 45 ms max.
10 ms max. *4
ON-state residual voltage 3.0 V max. (safety output, auxiliary output)
OFF-state leakage current 0.1 mA max. (safety output, auxiliary output)
Maximum wiring length of safety
input, logical AND connection input,
and Non-contact Door Switch input
100 m max. (External connection impedance: 100 Ω max. and 10 nF max.)
Reset input time
(Reset button pressing time)
100 ms min.
Accuracy of OFF-delay time *5 --- Within ±5% of the set value Within ±5% of the set value
Insulation
resistance
Between logical AND
connection terminals,
and power supply input
terminals and other input
and output terminals
connected together
20 MΩ min. (at 100 VDC)
---
Between all terminals
connected together and
DIN rail
100 MΩ min.
(at 500 VDC)
Dielectric
strength
Between logical AND
connection terminals,
and power supply input
terminals and other input
and output terminals
connected together
500 VAC for 1 min.
---
Between all terminals
connected together and
DIN rail
1,200 VAC for 1 min
Between different poles
of outputs
---
Between relay outputs
connected together and
other terminals
connected together
2,200 VAC for 1 min
Vibration resistance 10 to 55 to 10 Hz, 0.375 mm single amplitude (0.75 mm double amplitude)
Shock
resistance
Destruction 300 m/s
2
Malfunction 100 m/s
2
Durability
Electrical ---
100,000 cycles min. rated
load, switching frequency:
1,800 cycles/hour)
Mechanical ---
5,000,000 cycles min.
(switching frequency:
7,200 cycles/hour)
Ambient operating temperature 10 to 55°C (no icing or condensation)
Ambient operating humidity 25% to 85%
Terminal tightening torque 0.5 N·m (For the G9SX-NS@-RT (with screw terminals) only)
Weight Approx. 125 g Approx. 200 g Approx. 165 g