Datasheet

CP1L
26
Temperature Sensor Units: CP1W-TS001/TS002/TS101/TS102
By mounting a Temperature Sensor Unit to the PLC, inputs can be obtained from thermocouples or platinum resistance thermometers, and tem-
perature measurements can be converted to binary data and stored in the input area of the CPU Unit.
* Accuracy for a K-type sensor at -100°C or less is ±4°C ±1 digit max.
The rotary switch is used to set the temperature range.
Item
CP1W-TS001 CP1W-TS002 CP1W-TS101 CP1W-TS102
Thermocouples Platinum resistance thermometer
Temperature sensors
Switchable between K and J, but same type must be used for
all inputs.
Switchable between Pt100 and JPt100, but same type must
be used for all inputs.
Number of inputs 2424
Allocated input words 2424
Accuracy
(The larger of ±0.5% of converted value or ±2°C) ±1 digit
max. *
(The larger of ±0.5% of converted value or ±1°C) ±1 digit
max.
Conversion time 250 ms for 2 or 4 input points
Converted temperature data 16-bit binary data (4-digit hexadecimal)
Isolation Photocouplers between all temperature input signals
Current consumption 5 VDC: 40 mA max., 24 VDC: 59 mA max. 5 VDC: 54 mA max., 24 VDC: 73 mA max.
Setting
CP1W-TS001/TS002 CP1W-TS101/TS102
Input type Range (°C) Range (°F) Input type Range (°C) Range (°F)
0
K
200 to 1,300 300 to 2,300 Pt100 200.0 to 650.0 300.0 to 1,200.0
1 0.0 to 500.0 0.0 to 900.0 JPt100 200.0 to 650.0 300.0 to 1,200.0
2
J
100 to 850 100 to 1,500 ---
Cannot be set.3 0.0 to 400.0 0.0 to 750.0 ---
4 to F --- Cannot be set. ---