Datasheet

CP1E-E@@(S)D@-@ CP1E-N@@(S@)D@-@/NA20D@-@
35
Analog I/O Units
Temperature Sensors Units
* Accuracy for a K-type sensor at -100°C or less is ±4°C ±1 digit max.
The rotary switch is used to set the temperature range.
CompoBus/S I/O Link Unit
Model CP1W-MAD11
Item Voltage I/O Current I/O
Analog Input
Section
Number of inputs 2 inputs (2 words allocated)
Input signal range
0 to 5 VDC, 1 to 5 VDC,
0 to 10 VDC, or 10 to 10 VDC
0 to 20 mA or 4 to 20 mA
Max. rated input ±15 V ±30 mA
External input impedance 1 MΩ min. Approx. 250 Ω
Resolution 1/6000 (full scale)
Overall accuracy
25°C 0.3% full scale 0.4% full scale
0 to 55°C 0.6% full scale 0.8% full scale
A/D conversion data
16-bit binary (4-digit hexadecimal)
Full scale for 10 to 10 V: F448 to 0BB8 hex
Full scale for other ranges: 0000 to 1770 hex
Averaging function Supported (Settable for individual inputs via DIP switch)
Open-circuit detection function Supported
Analog Output
Section
Number of outputs 1 output (1 word allocated)
Output signal range
1 to 5 VDC, 0 to 10 VDC, or
10 to 10 VDC,
0 to 20 mA or 4 to 20 mA
Allowable external output load resistance 1 kΩ min. 600 Ω max.
External output impedance 0.5 Ω max.
Resolution 1/6000 (full scale)
Overall accuracy
25°C 0.4% full scale
0 to 55°C 0.8% full scale
Set data (D/A conversion)
16-bit binary (4-digit hexadecimal)
Full scale for 10 to 10 V: F448 to 0BB8 hex
Full scale for other ranges: 0000 to 1770 hex
Conversion time 2 ms/point (6 ms/all points)
Isolation method
Photocoupler isolation between analog I/O terminals and internal circuits.
No isolation between analog I/O signals.
Current consumption 5 VDC: 83 mA max., 24 VDC: 110 mA max.
Item CP1W-TS001 CP1W-TS002 CP1W-TS101 CP1W-TS102
Temperature sensors
Thermocouples Platinum resistance thermometer
Switchable between K and J, but same type must be used for
all inputs.
Switchable between Pt100 and JPt100, but same type must
be used for all inputs.
Number of inputs 2424
Allocated input words 2424
Accuracy
(The larger of ±0.5% of converted value or ±2°C) ±1 digit
max. *
(The larger of ±0.5% of converted value or ±1°C) ±1 digit
max.
Conversion time 250 ms for 2 or 4 input points
Converted temperature data 16-bit binary data (4-digit hexadecimal)
Isolation Photocouplers between all temperature input signals
Current consumption 5 VDC: 40 mA max., 24 VDC: 59 mA max. 5 VDC: 54 mA max., 24 VDC: 73 mA max.
Setting
CP1W-TS001/TS002 CP1W-TS101/TS102
Input type Range (°C) Range (°F) Input type Range (°C) Range (°F)
0
K
200 to 1,300 300 to 2,300 Pt100 200.0 to 650.0 300.0 to 1,200.0
1 0.0 to 500.0 0.0 to 900.0 JPt100 200.0 to 650.0 300.0 to 1,200.0
2
J
100 to 850 100 to 1,500 ---
Cannot be set.3 0.0 to 400.0 0.0 to 750.0 ---
4 to F --- Cannot be set. ---
Model number CP1W-SRT21
Master/slave CompoBus/S Slave
Number of I/O points 8 input points, 8 output points
Number of words allocated in CPU
Unit I/O memory
1 input word, 1 output word
Node number setting
Set using the DIP switch
(Set before turning on the CPU Unit’s power supply.)