Datasheet
201Analog I/O Unit
Programmable
Controllers
CJ1W-MAD42(SL)
Analog I/O Unit
Handles 4 Analog Inputs and 2 Analog
Outputs
• Conversion time: 3 ms for all 6 channels combined
• Resolution: 1/8000
Analog Inputs
• Wire burnout detection
• Peak hold function
• Mean function
• Offset gain setting
Analog Outputs
• Output hold
• Offset gain adjustment
Other Features
• Scaling function
Specifications
M
M
Preamp
Transducer
Sensor
Sensor
Temperature,
pressure, speed,
flowrate
Voltage, current,
power, power factor
Regulator
(Temperature control)
(Position control)
(Speed control)
Servo-
controller
Variable
speed
Chart
recorder
Voltage output 2 (+)
Output 2 (−)
Current output 2 (+)
N.C.
Input 2 (+)
Input 2 (−)
AG
Input 4 (+)
Input 4 (−)
Voltage output 1 (+)
Output 1 (−)
Current output 1 (+)
N.C.
Input 1 (+)
Input 1 (−)
AG
Input 3 (+)
Input 3 (−)
System Configuration Terminal Arrangement
Item Classification: Special I/O Unit
Inputs Outputs
Inputs/outputs 4 pts 2 pts
Signal range Voltages 1 to 5 V Yes
0 to 10 V Yes
0 to 5 V Yes
–10 to 10 V Yes
Currents 4 to 20 mA Yes
Input impedance Voltage inputs 1 MΩ, Current inputs 250 Ω ---
Maximum load current (for voltage outputs) 2.4 mA
Maximum load resistance (current outputs) 600 Ω
Signal range settings 4 settings (one for each point) 2 settings (one for each point)
Resolution 1/4000 (default), 1/8000 (selectable)
Conversion speed 1.0 ms/point (default) or 500 µs/point (selectable)
Overall accuracy (at 23 °C) Voltage: ±0.2%
Current: ±0.2%
Voltage: ±0.3%
Current: ±0.3%
Overall accuracy (0 to 55 °C) Voltage: ±0.5%
Current: ±0.6%
Connections Terminal block
Functions Wire burnout Yes ---
Peak hold Yes ---
Mean Yes ---
Output hold --- Yes
Scaling Yes
Unit No. 0 to 95
Y201-EN2-03.book Seite 201 Donnerstag, 30. März 2006 1:52 13