Datasheet

198 Programmable Controllers
CJ1W-AD@@@(SL)
Analog Input Units
Convert Analog Signals to Binary Data
Wire burnout detection
Peak-hold function
Mean function
Offset gain setting
Range selection per intput
1/8000 resolution
2 ms conversion time for 8 channels
Function
Convert input signals such as 1 to 5 V or 4 to 20 mA to binary values between 0000 and 1F40 Hex and store the results in the allocated words
each cycle. The ladder diagram can be used to transfer the data to the DM Area or the SCALING instructions (e.g., SCL(194)) can be used to scale
the data to the desired range.
System Configuration Terminal Arrangement
Specifications
Preamp
Transducer
Sensor
Sensor
Temperature,
pressure,
speed, flowrate
Voltage, cur-
rent, power,
power factor
Input 2 (+)
Input 2 ()
Input 4 (+)
Input 4 ()
AG
Input 6 (+)
Input 6 ()
Input 8 (+)
Input 8 ()
Input 1 (+)
Input 1 ()
Input 3 (+)
Input 3 ()
AG
Input 5 (+)
Input 5 ()
Input 7 (+)
Input 7 ()
Item Classification: Special I/O Unit
CJ1W-AD081-V1(SL) CH1W-AD041-V1(SL)
Inputs 8 pts 4 pts
Signal range Voltages 1 to 5 V Yes
0 to 10 V Yes
0 to 5 V Yes
–10 to 10 V Yes
Currents 4 to 20 mA Yes
Signal range settings 8 settings (one for each point) 4 settings (one for each point)
Resolution 1/4000 (default) or 1/8000 (selectable)
Conversion speed 1 ms/point (default), or 250 μs/point (selectable)
Overall accuracy (at 23 °C) Voltage: ±0.2%
Current: ±0.4%
Overall accuracy (0 to 55 °C) Voltage: ±0.4%
Current: ±0.6%
Connections Terminal block
Features Wire burnout detection Yes
Peak-hold function Yes
Averaging Yes
Unit No. 0 to 95