Datasheet
Temperature Input Units 197
Programmable 
Controllers
Specifications
Item Classification: Basic I/O Unit
CJ1W-TS561 (SL) CJ1W-TS562 (SL)
Inputs 6 points 
Input Type Thermocouple types J or K (IEC 60584) 3-wire RTD types Pt100 or Pt1000 (IEC 60751)
Measurement Range Type J: -100.0 to +850.0 °C, 
Type K:-200.0 to 1300.0 °C
Pt100/Pt1000: -200.0 to +650.0 °C
Input Assignment by DIP-switch, any combination of input types is possible
Output Data 16-bit signed integer, resolution 0.1 °C
Conversion time 40 ms to 400 ms per active input 
(depending on filter setting OFF / 50 Hz / 60 Hz / 10 Hz)
Accuracy +/- 0.5% of PV or +/- 0.7 °C, whichever is larger, +/- 1 digit max. +/- 0.5% of PV or +/- 0.8 °C, whichever is larger, +/- 1 digit max.
Cold Junction accuracy +/- 2.0 °C n.a.
Sensor connection terminal block, screw type or screwless clamp (model code + (SL))
Y201-EN2-03.book Seite 197 Donnerstag, 30. März 2006 1:52 13