Datasheet
196 Programmable Controllers
CJ1W-TS561/-TS562
Temperature Input Units
Connect up to 6 temperature sensors per Unit.
These Basic I/O units allow up to 6 temperature sensors to
be connected.
• Input types (TS561: thermocouple J/K, TS562 :
Pt100/Pt1000) can be selected per channel.
• The unit presents the temperature data in the basic
I/O area of the PLC occupying from 3 to 6 CIO
words.
• Cold junction compensation (TS561) is provided
internally.
• Adjustable filtering allows mains frequencies (50/60
Hz) to be suppressed.
• Broken wire (TC/RTD)and short-circuit alarms
(RTD) are provided as error code in the PLC, and by
LED indication.
• The unit does not provide galvanic isolation
between the input signals.
CJ1W-TS561(SL) CJ1W-TS562(SL)
System Configuration
Terminal arrangement
6 thermocouple
inputs (K,J)
CJ1W-TS561
6 platinum resistance
thermometer inputs
(Pt100, PT1000)
CJ1W-TS562
Input 2 (−)
Input 2 (+)
NC
NC
Input 4 (−)
Input 4 (+)
Input 6 (−)
Input 6 (+)
NC
Input 1 (−)
Input 1 (+)
NC
NC
Input 3 (−)
Input 3 (+)
Input 5 (−)
Input 5 (+)
NC
Input 2 B'
Input 2 B
Input 2 A
Input 4 B'
Input 4 B
Input 4 A
Input 6 B'
Input 6 B
Input 6 A
Input 1 B'
Input 1 B
Input 1 A
Input 3 B'
Input 3 B
Input 3 A
Input 5 B'
Input 5 B
Input 5 A
Y201-EN2-03.book Seite 196 Donnerstag, 30. März 2006 1:52 13