Datasheet

237PROFIBUS-DP slave unit
Programmable
Controllers
CJ1W-PRT21
PROFIBUS-DP slave unit
PROFIBUS-DP I/O link unit
Data link to any PLC data area
Simple configuration using max. data input
100 words and max. data output of 100 words.
Max. total exchanged data 180 words.
CJ1 special I/O unit
Status information overview in host PLC,
plus extensive diagnostics via PROFIBUS
Specifications
Installation Host PLC System CJ1
Maximum number of Units per
PLC system
40
Current consumption 400 mA (maximum) at 5V DC from PLC power supply
Weight 90 g (typical)
Environment Storage temperature -20°C to +70°C
Operating temperature 0°C to +55°C
Operating humidity 10 to 90% (non-condensing)
Conformance to EMC- and environmental
standards
EN50081-2
EN61131-2
User
Interface
Switch settings Special I/O Machine number (00-95) by 2 rotary switch
PROFIBUS-DP node address (00-99) by 2 rotary switches
LED Indicators Unit status: RUN (green LED), ERC (red LED)
Network status: COMM (green LED), BF (red LED)
CPU status: ERH (red LED)
PLC Interface No. of CIO words allocated PLC Unit: 1 word control data
Unit PLC: 1 word status data
No. of DM words allocated Unit PLC: 8 words of Unit setup information
Amount of I/O data per Unit Fixed:
2 words CIO area (one in, one out) for Unit status + control bits.
2 words status information from the host PLC, containing operation status and error code
(read from location A400). This information will be sent to the PROFIBUS master:
- as extended diagnostics, only at a change of data content.
- optionally, attached to the I/O data, each PROFIBUS cycle.
Variable:
2 user-defined areas for PROFIBUS I/O data, with the following restrictions:
- Up to 100 words input in one PLC area (CIO, H, D, EM).
- Up to 100 words output in one PLC area (CIO, H, D, EM).
- Inputs+outputs must be 180 words or less
Y201-EN2-03.book Seite 237 Donnerstag, 30. März 2006 1:52 13