Datasheet
CJ1W-OC/OA/OD
8
CJ1W-OA201 Triac Output Unit (8 Points)
* Terminal numbers A0 to A8 and B0 to B8 are used in the external connection and terminal-device variable diagrams. They are not printed on
the Units.
Note: Although 16 I/O bits (1 word) are allocated, only 8 of these can be used for external I/O.
Name 8-point Triac Output Unit with Terminal Block
Model CJ1W-OA201
Max. Switching
Capacity
0.6 A 250 VAC, 50/60 Hz (2.4 A/Unit)
Max. Inrush Current 15 A (pulse width: 10 ms max.)
Min. Switching
Capacity
50 mA 75 VAC
Leakage Current 1.5 mA (200 VAC) max.
Residual Voltage 1.6 VAC max.
ON Response Time 1 ms max.
OFF Response Time 1/2 of load frequency + 1 ms or less.
Number of Circuits 8 (8 points/common, 1 circuit)
Surge Protector C.R Absorber + Surge Absorber
Fuses
5 A (1/common, 1 used)
The fuse cannot be replaced by the user.
Insulation Resistance
20 MΩ between the external terminals and the GR terminal (500 VDC)
Dielectric Strength 2,000 VAC between the external terminals and the GR terminal for 1 minute at a leakage current of 10 mA max.
Internal Current
Consumption
220 mA max.
Weight 150 g max.
Circuit Configuration
• The signal names of the terminals are the device variable names.
The device variable names are the names that use "Jxx" as the device name.
External connection
and terminal-device
variable diagram
• The signal names of the terminals are the device variable names.
The device variable names are the names that use "Jxx" as the device name.
Output indicator
Internal circuits
Fuse
to
Signal
name
COM
Jxx_Ch1_Out00
Jxx_Ch1_Out07
250 VAC max.
Signal
name
Connec-
tor pin
*
B0
B1
B2
B3
B4
B5
B6
B7
B8
A0
A1
A2
A3
A4
A5
A6
A7
A8
NC
NC
NC
NC
NC
NC
NC
NC
NC
L
L
L
L
L
L
L
L
COM
Jxx_Ch1_Out00
Jxx_Ch1_Out01
Jxx_Ch1_Out02
Jxx_Ch1_Out03
Jxx_Ch1_Out04
Jxx_Ch1_Out05
Jxx_Ch1_Out06
Jxx_Ch1_Out07