Datasheet
7
CJ1W-OC/OA/OD
CJ1W-OC211 Contact Output Unit (16 Points)
* Terminal numbers A0 to A8 and B0 to B8 are used in the external connection and terminal-device variable diagrams. They are not printed on
the Units.
Name 16-point Contact Output Unit with Terminal Block
Model CJ1W-OC211
Max. Switching
Capacity
2 A 250 VAC (cosφ = 1), 2 A 250 VAC (cosφ = 0.4), 2 A 24 VDC (8 A/Unit)
Min. Switching
Capacity
1 mA 5 VDC
Relays NY-24W-K-IE (Fujitsu Takamizawa Components, Ltd.), Cannot be replaced.
Service Life of Relay
Electrical: 150,000 operations (24 VDC, resistive load)/ 100,000 operations (250 VAC, cosφ = 0.4, inductive load)
Mechanical: 20,000,000 operations
Service life will vary depending on the connected load.
ON Response Time 15 ms max.
OFF Response Time 15 ms max.
Number of Circuits 16 points/common, 1 circuit
Insulation Resistance
20 MΩ between external terminals and the GR terminal (500 VDC)
Dielectric Strength 2,000 VAC between the external terminals and the GR terminal for 1 minute at a leakage current of 10 mA max.
Internal Current
Consumption
110 mA 5 VDC max.
96 mA 24 VDC max. (6 mA × No. of ON points)
Weight 170 g max.
Circuit Configuration
• The signal names of the terminals are the device variable names.
The device variable names are the names that use "Jxx" as the device name.
External connection
and terminal-device
variable diagram
• The signal names of the terminals are the device variable names.
The device variable names are the names that use "Jxx" as the device name.
Output indicator
Internal circuits
to
Signal
name
Jxx_Ch1_Out15
Jxx_Ch1_Out00
COM
COM
2 A 250 VAC,
2 A 24 VDC max.
Signal
name
Signal
name
Connec-
tor pin
*
B1
B2
B3
B4
B5
B6
B7
B8
A1
A2
A3
A4
A5
A6
A7
A8
B0
A0
L
L
L
L
L
L
L
L
L
L
L
L
L
L
L
L
Jxx_Ch1_Out01
Jxx_Ch1_Out03
Jxx_Ch1_Out05
Jxx_Ch1_Out07
Jxx_Ch1_Out09
Jxx_Ch1_Out11
Jxx_Ch1_Out13
Jxx_Ch1_Out15
Jxx_Ch1_Out00
Jxx_Ch1_Out02
Jxx_Ch1_Out04
Jxx_Ch1_Out06
Jxx_Ch1_Out08
Jxx_Ch1_Out10
Jxx_Ch1_Out12
Jxx_Ch1_Out14
COM
COM