Datasheet
23
CJ1W-OC/OA/OD
CJ1W-OD232 Transistor Output Unit (32 Points)
Name 32-point Transistor Output Unit with MIL Connector (Sourcing Outputs)
Model CJ1W-OD232
Rated Voltage 24 VDC
Operating Load
Voltage Range
20.4 to 26.4 VDC
Maximum Load
Current
0.5 A/point, 2.0 A/common, 4.0 A/Unit
Leakage Current 0.1 mA max.
Residual Voltage 1.5 V max.
ON Response Time 0.5 ms max.
OFF Response Time 1.0 ms max.
Load Short-circuit
Protection
Detection current: 0.7 to 2.5 A
Automatic restart after error clearance.
Insulation Resistance
20 MΩ between the external terminals and the GR terminal (100 VDC)
Dielectric Strength 1,000 VAC between the external terminals and the GR terminal for 1 minute at a leakage current of 10 mA max.
Number of Circuits 32 (16 points/common, 2 circuits)
Internal Current
Consumption
5 VDC 150 mA max.
External Power
Supply
20.4 to 26.4 VDC, 70 mA min.
Weight 80 g max.
Accessories None
Circuit Configuration
• When overcurrent is detected, the ERR indicator will light, and the corresponding bit (bit allocated for each common)in the Basic I/O Unit
Information Area (A050 to A069)will change to TRUE.
• The signal names of the terminals are the device variable names.
The device variable names are the names that use "Jxx" as the device name.
Wd m
Wd m+1
to
to
Output indicator
Internal circuits
ERR indicator
Allocated
CIO word
Signal name
Jxx_Ch1_Out15
Jxx_Ch1_Out00
0 V
Jxx_Ch2_Out00
Jxx_Ch2_Out15
0 V
SW
COM0 (+V)
COM0 (+V)
COM1 (+V)
COM1 (+V)
Short-circuit
protection
Short-circuit
protection