Datasheet
19
CJ-Series analog I/O and control units
Modular PLC
From basic analogue I/O to advanced
temperature control
The CJ-series offers a wide choice of analogue input units, fit for any application,
from low-speed, multi-channel temperature measurement to high-speed, high-accu-
racy data acquisition. Analogue outputs can be used for accurate control or external
indication.
Advanced units with built-in scaling, filtering and alarm functions reduce the need for
complex PLC programming. High-accuracy process I/O units support an extensive
range of sensors, for fast and accurate data acquisition. Temperature control units
relieve the PLC CPU of PID calculations and alarm monitoring. These functions are
handled autonomously by the unit, offering control performance and autotuning func-
tions similar to stand-alone temperature controllers.
Ordering information
Points Type Ranges Resolution Accuracy
*1
Conversion
time
Width Remarks Connection
type
Order code
4 Universal analogue
input
0 to 5 V
1 to 5 V
0 to 10 V
0 to 20 mA
4 to 20 mA
K, J, T, L, R, S, B
Pt100, Pt1000,
JPt100
V / I: 1/12000
T/C: 0.1 °C
RTD: 0.1 °C
V: 0.3%
I: 0.3%
T/C: 0.3%
RTD: 0.3%
250 ms/4 point 31 mm Universal inputs, with zero/span adjustment,
configurable alarms, scaling, sensor error
detection
M3 CJ1W-AD04U
Screwless CJ1W-AD04U(SL)
4 Analogue input 0 to 5 V,
0 to 10 V,
-10 to 10 V,
1 to 5 V,
4 to 20 mA
1/8,000 V: 0.2%
I: 0.4%
250 µs/point 31 mm Offset/gain adjustment, peak hold,
moving average, alarms
M3 CJ1W-AD041-V1
Screwless CJ1W-AD041-V1 (SL)
4 High-speed
analogue input
1 to 5 V,
0 to 10 V,
-5 to 5 V,
-10 to 10 V,
4 to 20 mA
1/40,000 V: 0.2%
I: 0.4%
35 µs/4 points 31 mm Direct conversion (CJ2H special instruction) M3 CJ1W-AD042
8 Analogue input 1 to 5 V,
0 to 10 V,
-10 to 10 V,
1 to 5 V,
4 to 20 mA
1/8,000 V: 0.2%
I: 0.4%
250 µs/point 31 mm Offset/gain adjustment, peak hold,
moving average, alarms
M3 CJ1W-AD081-V1
Screwless CJ1W-AD081-V1 (SL)
2 Analogue output 0 to 5 V,
0 to 10 V,
-10 to 10 V,
1 to 5 V,
4 to 20 mA
1/4,000 V: 0.3%
I: 0.5%
1 ms/point 31 mm Offset/gain adjustment, output hold M3 CJ1W-DA021
Screwless CJ1W-DA021 (SL)
4 Analogue output 1 to 5 V,
0 to 10 V,
-10 to 10 V,
1 to 5 V,
4 to 20 mA
1/4,000 V: 0.3%
I: 0.5%
1 ms/point 31 mm Offset/gain adjustment, output hold M3 CJ1W-DA041
Screwless CJ1W-DA041 (SL)
4 High-speed
analogue output
1 to 5 V,
0 to 10 V,
-10 to 10 V
1/40,000 0.3% 35 µs/4 points 31 mm Direct conversion (CJ2H special instruction) M3 CJ1W-DA042V
8 Voltage output 0 to 5 V,
0 to 10 V,
-10 to 10 V,
1 to 5 V
1/8,000 0.3% 250 µs/point 31 mm Offset/gain adjustment, output hold M3 CJ1W-DA08V
Screwless CJ1W-DA08V (SL)
8 Current output 4 to 20 mA 1/8,000 0.5% 250 µs/point 31 mm Offset/gain adjustment, output hold M3 CJ1W-DA08C
Screwless CJ1W-DA08C (SL)
4 + 2 Analogue in + out-
put
1 to 5 V,
0 to 10 V,
-10 to 10 V,
1 to 5 V,
4 to 20 mA
1/8,000 in: 0.2%
out: 0.3%
1 ms/point 31 mm Offset/gain adjustment, scaling, peak hold,
moving average, alarms, output hold
M3 CJ1W-MAD42
Screwless CJ1W-MAD42 (SL)
4 Universal analogue
input
DC voltage,
DC current,
Thermocouple,
Pt100/Pt1000,
potentiometer
1/256000 0.05% 60 ms/4 points 31 mm All inputs individually isolated, configurable
alarms, maintenance functions,
user-defined scaling, zero/span adjustment
M3 CJ1W-PH41U
2 Process input 4 to 20 mA
0 to 20 mA
0 to 10 V,
-10 to 10 V,
0 to 5 V,
-5 to 5 V,
1 to 5 V,
0 to 1.25 V,
1.25 to 1.25 V
1/64,000 0.05% 5 ms/point 31 mm Configurable alarms, maintenance
functions, user-defined scaling, zero/span
adjustment, square root, totaliser
M3 CJ1W-PDC15