Datasheet
12 Frequency inverters
Three-phase 200 V class
Three-phase 400 V class
Input AC Reactor
DC Reactor
Output AC
Reactor
Model 3G3MX2 A2001 A2002 A2004 A2007 A2015 A2022 A2037 A2055 A2075 A2110 A2150
Inverter
capacity
kVA
200 VT
0.4 0.6 1.2 2.0 3.3 4.1 6.7 10.3 13.8 19.3 23.9
200 CT
0.2 0.5 1.0 1.7 2.7 3.8 6.0 8.6 11.4 16.2 20.7
240 VT
0.4 0.7 1.4 2.4 3.9 4.9 8.1 12.4 16.6 23.2 28.6
240 CT
0.3 0.6 1.2 2.0 3.3 4.5 7.2 10.3 13.7 19.5 24.9
Rated current (A) VT
1.2 1.9 3.4 6.0 9.6 12.0 19.6 30.0 40.0 56.0 69.0
Rated current (A) CT
1.0 1.6 3.0 5.0 8.0 11.0 17.5 25.0 33.0 47.0 60.0
Total heat loss
12 22 30 48 79 104 154 229 313 458 625
Efficiency at rated load
89.5 90 93 94 95 95.5 96 96 96 96 96
Cooling Method Self cooling
Forced-air-cooling
Model 3G3MX2 A4004 A4007 A4015 A4022 A4030 A4040 A4055 A4075 A4110 A4150
Inverter
capacity
kVA
380V VT
1.3 2.6 3.5 4.5 5.7 7.3 11.5 15.1 20.4 25.0
380V CT
1.1 2.2 3.1 3.6 4.7 6.0 9.7 11.8 15.7 20.4
480V VT
1.7 3.4 4.4 5.7 7.3 9.2 14.5 19.1 25.7 31.5
480V CT
1.4 2.8 3.9 4.5 5.9 7.6 12.3 14.9 19.9 25.7
Rated current (A) VT
2.1 4.1 5.4 6.9 8.8 11.1 17.5 23.0 31.0 38.0
Rated current (A) CT
1.8 3.4 4.8 5.5 7.2 9.2 14.8 18.0 24.0 31.0
Total heat loss 35 56 96 116 125 167 229 296 411 528
Efficiency at rated load 92 93 94 95 96 96 96 96.2 96.4 96.6
Cooling Method Self cooling Forced-air-cooling
1 phase 200 V class 3 phase 200 V class 400 V class
Max. ap-
plicable
motor
output kW
Reference
Current
value
A
Induc-
tance
mH
Max. ap-
plicable
motor
output kW
Reference
Current
value
A
Induc-
tance
mH
Max. ap-
plicable
motor out-
put kW
Reference
Current
value
A
Induc-
tance
mH
0.4 AX-RAI02000070-DE 7.0 2.0 1.5 AX-RAI02800080-DE 8.0 2.8 1.5 AX-RAI07700050-DE
5.0 7.7
0.75 AX-RAI01700140-DE 14.0 1.7 3.7 AX-RAI00880200-DE 20.0 0.88 4.0 AX-RAI03500100-DE 10.0 3.5
1.5 AX-RAI01200200-DE 20.0 1.2 7.5 AX-RAI00350335-DE 33.5 0.35 7.5 AX-RAI01300170-DE
17.0 1.3
2.2 AX-RAI00630240-DE 24.0 0.63 15 AX-RAI00180670-DE 67.0 0.18 15 AX-RAI00740335-DE
33.5 0.74
200 V class 400 V class
Max. applicable
motor output kW
Reference
Current value
A
Inductance
mH
Max. applicable
motor output kW
Reference
Current value
A
Inductance
mH
0.2 AX-RC21400016-DE 1.6 21.4 0.4 AX-RC43000020-DE
2.0 43.0
0.4 AX-RC10700032-DE 3.2 10.7 0.7 AX-RC27000030-DE 3.0 27.0
0.7 AX-RC06750061-DE 6.1 6.75 1.5 AX-RC14000047-DE
4.7 14.0
1.5 AX-RC03510093-DE 9.3 3.51 2.2 AX-RC10100069-DE 6.9 10.1
2.2 AX-RC02510138-DE 13.8 2.51 3.0 AX-RC08250093-DE 9.3 8.25
3.7 AX-RC01600223-DE 22.3 1.60 4.0 AX-RC06400116-DE 11.6 6.40
5.5 AX-RC01110309-DE 30.9 1.11 5.5 AX-RC04410167-DE 16.7 4.41
7.5 AX-RC00840437-DE 43.7 0.84 7.5 AX-RC03350219-DE 21.9 3.35
11.0 AX-RC00590614-DE 61.4 0.59 11.0 AX-RC02330307-DE 30.7 2.33
15.0 AX-RC00440859-DE 85.9 0.44 15.0 AX-RC01750430-DE 43.0 1.75
200 V class 400 V class
Max. applicable
motor output kW
Reference
Current value
A
Inductance
mH
Max. applicable
motor output kW
Reference
Current value
A
Inductance
mH
0.4 AX-RAO11500026-DE 2.6 11.50
1.5 AX-RAO16300038-DE
3.8 16.30
0.75 AX-RAO07600042-DE 4.2 7.60
1.5 AX-RAO04100075-DE 7.5 4.10
2.2 AX-RAO03000105-DE 10.5 3.00 2.2 AX-RAO11800053-DE 5.3 11.80
3.7 AX-RAO01830160-DE 16.0 1.83 4.0 AX-RAO07300080-DE
8.0 7.30
5.5 AX-RAO01150220-DE 22.0 1.15 5.5 AX-RAO04600110-DE 11.0 4.60
7.5 AX-RAO00950320-DE 32.0 0.95 7.5 AX-RAO03600160-DE 16.0 3.60
11 AX-RAO00630430-DE 43.0 0.63 11 AX-RAO02500220-DE 22.0 2.50
15 AX-RAO00490640-DE 64.0 0.49 15 AX-RAO02000320-DE 32.0 2.00
MCCB
Power supply
AC reactor
MX2
R/L1U
V
W
X
Y
Z
S/L2
T/L3
Power
supply
MX2
DC reactor
R/L1
+1 P/+2
MCCB
S/L2
T/L3