Specifications
Certified Standard Ratings
• UL, cUL (File No. E41515)
6 A at 220 VAC, 10 A at 110 VAC
• TÜV (EN60947-5-1) (Low Voltage Directive)
3 A at 220 VAC
• CCC (GB14048.5)
3 A at 240 VAC, 1.5 A at 24 VDC
Certified Standards
Note:
Only models with NC contacts have a direct opening mechanism.
*1. UL-certification for CSA C22.2 No. 14 has been obtained.
Certification has been obtained for individual Switch Blocks and
Lighting Units.
*2. Some models have been certified.
Ratings
Contacts (Standard Load)
Note: 1. Rated current values are determined according to the
testing conditions. The above ratings were obtained by
conducting tests under the following conditions.
(1) Ambient temperature: 20°±2°C
(2) Ambient humidity: 65±5%
(3) Operating frequency: 20 operations/minute
2. Minimum applicable load: 10 mA at 5 VDC
LED Lamp
Voltage-reduction lighting
Characteristics
*1. With no icing or condensation.
*2. The degree of protection from the front of the panel.
*3. The degree of protection is IP65 even with an integrated control box, but the system is not oil resistant.
Certification
body
Standards File No.
UL *1
UL508, C22.2 No.14
E41515
TÜV SÜD
EN60947-5-1
(Certified direct opening),
EN60947-5-5
Consult your OMRON
representative for details.
CQC (CCC) GB14048.5 2003010303070635
KOSHA *2 EN60947-5-1
Consult your OMRON
representative for details.
Rated carry
current (A)
Rated
voltage
(V)
Rated current (A)
AC15
(Inductive
load)
AC12
(Resistive
load)
DC13
(Inductive
load)
DC12
(Resistive
load)
10
24 VAC 10 10
--- ---
110 VAC 5 10
220 VAC 3 6
380 VAC 2 3
440 VAC 1 2
24 VDC
--- ---
1.5 10
110 VDC 0.5
2
220 VDC 0.2
0.6
380 VDC 0.1
0.2
Rated voltage Operating voltage Current value
6 VAC/VDC 6 VAC/VDC ± 5%
Approx. 8 mA12 VAC/VDC 12 VAC/VDC ± 5%
24 VAC/VDC 24 VAC/VDC ± 5%
Rated voltage Operating voltage Rated current
Applicable lamp
(BA9S/Base: 13)
110 VAC
100 VAC
(95 to 115 V)
Approx. 8 mA
LED lamp
A22-24A@
220 VAC
200 VAC
(190 to 230 V)
Type Turn-reset Pull-reset
Item Non-lighted model Lighted model Non-lighted model
Allowable operating
frequency
Mechanical 30 operations/minute (One operation consists of set and reset operations.)
Electrical 30 operations/minute (One operation consists of set and reset operations.)
Insulation resistance 100 MΩ min. (at 500 VDC)
Contact resistance 100 mΩ max. (initial value)
Dielectric strength
Between terminals of same polarity 2,500 VAC, 50/60 Hz for 1 min.
Between each terminal and ground 2,500 VAC, 50/60 Hz for 1 min.
Vibration resistance 10 to 55 Hz, 1.5-mm double amplitude (contact separation within 1 ms)
Shock resistance
Destruction 1000 m/s
2
Malfunction 250 m/s
2
max. (contact separation within 1 ms)
Durability
Mechanical 300,000 operations min. (One operation consists of set and reset operations.)
Electrical 300,000 operations min. (One operation consists of set and reset operations.)
Ambient operating temperature *1 -20 to +70°C -20 to +55°C -20 to +70°C
Ambient operating humidity 35 to 85% RH
Ambient storage temperature -40 to +70°C
Degree of protection
IP65 oil-resistant models
*2 *3 IP65 *2
IP65 oil-resistant models
*2 *3
Electric shock protection class Class II
PTI (tracking characteristic) 175
Degree of contamination 3 (EN60947-5-1)
Minimum direct opening stroke 11 mm
Minimum direct opening force 45 N
Conditional short-circuit current 100 A (EN 60947-5-1)
Weight (for a 40-dia. head 1NC/1NO Operation Unit) Approx. 65 g Approx. 80 g Approx. 100 g