Datasheet

G-310 Safety Sensors / Components
Specifications
Approved Standards
Note: UL-approved for CSA C22.2 No. 14 and bears the cR mark.
Approved Standard Ratings
UL, cUL (File No. E41515)
6 A at 220 V, 10 A at 110 VAC
EN60947-5-1 (Low Voltage Directive)
Rated current: 10 A; Rated voltage: 220 VAC
Ratings
Contacts (Standard Load)
Note: 1. Rated current values are determined according to the test-
ing conditions. The above ratings were obtained by con-
ducting tests under the following conditions.
(1) Ambient temperature: 20×±2°C
(2) Ambient humidity: 65±5%
(3) Operating frequency: 20 operations/minute
2. Minimum applicable load: 10 mA at 5 VDC
Contacts (Microload)
LED Indicators without Voltage Reduction Unit
Super-bright LED Indicator
Incandescent Lamp
Voltage-reduction Lighting
Recognized
organization
Standards File No.
UL (See note.) UL508 E41515
AZCO EN60947-5-1 C9805502
Rated
carry
current
Rated
voltage
Rated current (A)
AC15
(induc-
tive load)
AC12
(resistive
load)
DC13
(induc-
tive load)
DC12
(resis-
tive load)
10
24 VAC 10 10
--- ---
110 VAC 5 10
220 VAC 3 6
380 VAC 2 3
440 VAC 1 2
24 VDC
--- ---
1.5 10
110 VDC 0.5 2
220 VDC 0.2 0.6
380 VDC 0.1 0.2
Rated applicable load Minimum applicable load
50 mA at 5 VDC
(Resistive load)
1 mA at 5 VDC
Rated voltage Rated current Operating voltage
6 VDC 60 mA 6 VDC±5%
6 VAC 60 mA 6 VAC/VDC±5%
12 VAC/VDC 30 mA 12 VAC/VDC±5%
24 VAC/VDC 15 mA 24 VAC/VDC±5%
Rated voltage Rated current Operating voltage
24 VAC/VDC 15 mA 24 VAC/VDC ±5%
Rated voltage Rated current Operating voltage
6 VAC/VDC 200 mA 5 VAC/VDC
14 VAC/VDC 80 mA 12 VAC/VDC
28 VAC/VDC 40 mA 24 VAC/VDC
130 VAC/VDC 20 mA 100 VAC/VDC
Rated voltage Operational voltage
Applicable lamp
(BA9S/13# gold)
110 VAC 95 to 115 VAC
LED Lamp
(A22-24A#)
220 VAC 190 to 230 VAC