Datasheet
10 Frequency inverters
Standard connections
Terminal Block Specifications
Terminal Name Function (signal level)
R/L1, S/L2, T/L3
Main circuit power supply input Used to connect line power to the drive.
Drives with single-phase 200 V input power use only terminals R/L1 and N (T/L3), terminal 
S/L2 is not available for these units
U/T1, V/T2, W/T3
Inverter output Used to connect the motor
PD/+1, P/+
External DC reactor terminal Normally connected by the short-circuit bar. Remove the short-circuit bar between +1 and P/
+2 when a DC reactor is connected.
P/+, N/-
Regenerative braking unit terminal
Connect optional regenerative braking units (If a braking torque is required)
P/+, RB
Braking resistor terminals
Connect option braking resistor (if a braking torque is required)
Grounding For grounding (grounding should conform to the local grounding code.)
Input
circuits 
24V 
P24 
+ - 
1 
2 
3/GS1
4/GS2
5/PTC
Forward 
Thermistor  
GND for logic inputs 
AM 
Meter 
H 
L 
Analog reference 
0~10VDC 
4~20mA 
GND for analog signals 
MX2  
Motor 
PD/+1
P/+ 
R 
(L1) 
S 
(L2) 
T 
N(L3) 
U
(T1) 
V
(T2) 
W
(T3) 
N/- 
AL2
AL0 
AL1 
6 
7/EB
EO 
Meter 
RB 
11/EDM
Load 
Freq. arrival signal 
Open collector output 
Output circuit 
GND for logic outputs 
12 
Load 
+ 
- 
CM2 
L 
L 
+ 
- 
O 
OI 
EA 
Apprx.10k 
10Vdc 
Apprx.100 
L 
L 
Option port connector 
L 
L 
L 
L 
L 
L 
SP 
SN 
) 
L 
PLC 
Short bar
(Source type) 
Breaker, MCCB 
or GFI
Power source, 
3-phase or 
1-phase, per 
inverter model
Intelligent inputs, 
7 terminals
NOTE: For the wiring 
of intelligent I/O and 
analog inputs, be sure 
to use twisted pair/
shielded cable. Attach 
the shielded wire for 
each signal to its 
respective common 
terminal at the inverter 
end only.
Input impedance of 
each intelligent input is 
4.7k 
[5] configurable as 
discrete input or 
thermistor input
Pulse train input 
24Vdc 32kHz max.
RS485 
transceiver
USB 
transceiver
Option port 
controller
USB (mini-B) port 
(PC communication port) 
USB power: Self power
RJ45 port
(Optional operator port)
RS485 
transceiver
Serial communication port 
(RS485/ModBus)
Termination resistor (200
(Change by slide switch)
Relay contacts, 
type 1 Form C
Brake 
resistor 
(optional)
Braking
unit
(optional)
DC reactor 