Datasheet

18 DC Power Relays (25-A Models) G9EB-1
Specifications
Ratings
Coil
Note: 1. The figures for the rated current and coil resistance are for a coil temperature of 23°C and have a tolerance of ±10%.
2. The figures for the operating characteristics are for a coil temperature of 23
°C.
3. The figure for the maximum voltage is the maximum voltage that can be applied to the relay coil.
Contacts
Characteristics
Note: 1. The above values are initial values at an ambient temperature of 23°C unless otherwise specified.
2. The contact resistance was measured with 1 A at 5 VDC using the voltage drop method.
3. The insulation resistance was measured with a 500-VDC megohmmeter.
4. The impulse withstand voltage was measured with a JEC-212 (1981) standard impulse voltage waveform (1.2
× 50 µs).
5. The mechanical endurance was measured at a switching frequency of 3,600 operations/hr.
6. The electrical endurance was measured at a switching frequency of 60 operations/hr.
7. These values are for when a varistor is used as the protective circuit against reverse surge in the relay coil. Using a diode will reduce the
switching characteristics.
Rated voltage Rated current Coil resistance Must-operate
voltage
Must-release
voltage
Maximum voltage
(See note 3.)
Power
consumption
12 VDC 166.7 mA 72
75% max. of rated
voltage
10% min. of rated
voltage
130% of rated volt-
age (at 23°C within
10 minutes)
Approx. 2 W
24 VDC 83.3 mA 288
48 VDC 41.7 mA 1,152
60 VDC 33.3 mA 1,800
100 VDC 20 mA 5,000
Item Resistive load
G9EB-1(-B)
Rated load 25 A at 250 VDC
Rated carry current 25 A
Maximum switching voltage 250 V
Maximum switching current 25 A
Item G9EB-1-B
Contact resistance (See note 2.)
30 m max.
Contact voltage drop 0.1 V max. (for a carry current of 25 A)
Operate time
30 ms max.
Release time
15 ms max.
Insulation resistance
(See note 3.)
Between coil and contacts
1,000 M min.
Between contacts of the same polarity
1,000 M min.
Dielectric strength Between coil and contacts
2,500 VAC, 1 min
Between contacts of the same polarity
2,500 VAC, 1 min
Impulse withstand voltage (See note 4.)
4,500 V
Vibration resistance Destruction
10 to 55 to 10 Hz, 0.75-mm single amplitude (Acceleration: 2.94 to 88.9 m/s
2
)
Malfunction
10 to 55 to 10 Hz, 0.75-mm single amplitude (Acceleration: 2.94 to 88.9 m/s
2
)
Shock resistance Destruction
490 m/s
2
Malfunction
100 m/s
2
Mechanical endurance (See note 5.)
100,000 operations min.
Electrical endurance (resistive load) (See note 6 and 7.)
250 VDC, 25 A, 30,000 ops. min.
Short-time carry current 50 A (5 min), 40 A (10 min)
Maximum interruption current (See note 7.) 100 A at 250 VDC (5 times)
Overload interruption (See note 7.) 50 A at 250 VDC (50 times min.)
Ambient operating temperature
40 to 70°C (with no icing or condensation)
Ambient operating humidity 5% to 85%
Weight (including accessories) Approx. 135 g