Datasheet
191
Text
190
Text PCB Signal Relay – G6E
■
Contact Ratings
Load Resistive load (cosϕ = 1) Inductive load (cosφ = 0.4; L/R = 7 ms)
Rated Load 0.4 A at 125 VAC; 2 A at 30 VDC 0.2 A at 125 VAC; 1 A at 30 VDC
Contact Material Ag (Au alloy)
Rated Carry Current 3 A
Max. switching voltage 250 VAC, 220 VDC
Max. switching current 3 A
Max. switching power 50 VA, 60 W 25 VA, 30 W
Failure rate (reference value) 10µ A at 10m VDC
Note: P level: λ
60
= 0.1 x 10
-6
/operation.
This value was measured at a switching frequency of 120 operations/min and the criterion is 50 Ω. This value may vary
depending on the operating environment. Always double-check relay suitability under actual operating conditions.
■
Approved Standards
UL508 (File No. E41515)/CSA C22.2, No.14 (File No. LR31928)
Contact form Coil ratings Contact ratings
SPDT 3 to 48 VDC 0.2 A, 250 VAC (general use)
0.6 A, 125 VAC (general use)
2 A, 30 VDC (resistive)
0.6 A, 125 VDC (resistive, Ag contact only)
■
Characteristics
Contact resistance (see note 1) 50 mΩ max.
Operate (set*) time (see note 2) 5 ms max. (mean value: approx. 2.9 ms; 48 VDC type: approx. 2.4 ms)
Release (reset*) time (see note 2) 5 ms max. (mean value: approx. 1.3 ms)
Max. operating frequency Mechanical: 36,000 operations/hr
Electrical: 1,800 operations/hr (under rated load)
Insulation resistance (see note 3) 1,000 MΩ min. (at 500 VDC)
Dielectric 1,500 VAC, 50/60 Hz for 1 min between coil and contacts
withstand voltage 1,000 VAC, 50/60 Hz for 1 min between contacts of same polarity
Impulse withstand voltage 1,500 V (10 x 160 µs) (conforms to FCC Part 68)
Vibration resistance Destruction: 10 to 55 to 10 Hz, 2.5mm single amplitude (5mm double amplitude)
Malfunction: 10 to 55 to 10 Hz, 1.65mm single amplitude (3.3mm double amplitude)
Shock resistance Destruction: 1,000 m/s
2
Malfunction: 300 m/s
2
Endurance Mechanical: 100,000,000 operations min. (at 36,000 operations/hr)
Electrical: 100,000 operations min. (0.4 A at 125 VAC resistive load;
0.2 A at 125 VAC inductive load)
500,000 operations min. (2 A at 30 VDC resistive load; 1 A at 30 VDC inductive load)
200,000 operations min. (3 A at 30 VDC resistive load)
Ambient temperature Operating: -40°C to 70°C (with no icing)
Ambient humidity 5% to 85%
Weight Approx. 2.7 g
Note: Values here are initial values.
1. The contact resistance was measured with 1A at 5VDC using a voltage-drop methhod.
2. Values in parentheseses are actual values.
3. The insulation resistance was measured with a 500VDC megohmeter applied to the same parts as tose used for checking the
dielectric strength.
Signal Relays
PCB Signal Relay – G6E
Specifications
■
Coil Ratings
Single-side Stable, Bifurcated Crossbar Contact Type
Rated voltage 3 VDC 5 VDC 6 VDC 9 VDC 12 VDC 24 VDC 48 VDC
Rated current 66.7 mA 40 mA 33.3 mA 22.2 mA 16.7 mA 8.3 mA 8.3 mA
Coil resistance 45 Ω 125 Ω 180 Ω 405 Ω 720 Ω 2,880 Ω 5,760 Ω
Coil inductance Armature OFF
0.08 0.18 0.31 0.62 1.20 4.70 5.35
(H) (ref. value) Armature ON
0.06 0.17 0.24 0.50 0.99 3.90 5.12
Must operate voltage 70% max. of rated voltage
Must release voltage 10% min. of rated voltage
Max. voltage 190% of rated voltage at 23°C 170% of rated
voltage at 23°C
Power consumption Approx. 200 mW Approx 400 mW
Single-winding Latching, Bifurcated Crossbar Contact Type
Rated voltage 3 VDC 5 VDC 6 VDC 9 VDC 12 VDC 24 VDC
Rated current 66.7 mA 40 mA 33.3 mA 22.2 mA 16.7 mA 8.3 mA
Coil resistance 45 Ω 125 Ω 180 Ω 405 Ω 720 Ω 2,880 Ω
Coil inductance Armature OFF
0.05 0.13 0.19 0.45 0.84 3.56
(H) (ref. value) Armature ON
0.04 0.12 0.17 0.40 0.79 3.10
Must set voltage 70% max. of rated voltage
Must reset voltage 70% max. of rated voltage
Max. voltage 190% of rated voltage at 23°C
Power consumption Approx. 200 mW
Double-winding Latching, Bifurcated Crossbar Contact Type
Rated voltage 3 VDC 5 VDC 6 VDC 9 VDC 12 VDC 24 VDC
Rated current 66.7 mA 40 mA 33.3 mA 22.2 mA 16.7 mA 8.3 mA
Coil resistance 45 Ω 125 Ω 180 Ω 405 Ω 720 Ω 2,880 Ω
0.03 0.09 0.12 0.25 0.44 1.66
0.03 0.08 0.11 0.22 0.41 1.62
Rated current 66.7 mA 40 mA 33.3 mA 22.2 mA 16.7 mA 8.3 mA
Coil resistance 45 Ω 125 Ω 180 Ω 405 Ω 720 Ω 2,880 Ω
0.03 0.09 0.12 0.25 0.44 1.66
0.03 0.08 0.11 0.22 0.41 1.62
Must set voltage 70% max. of rated voltage
Must reset voltage 70% max. of rated voltage
Max. voltage 190% of rated voltage (at 23°C)
Power consumption Set coil: Approx. 200 mW
Reset coil: Approx. 200 mW
Note: 1. The rated current and coil resistance are measured at a coil temperature of 23°C with a tolerance of ±10%.
2. Operating characteristics are measured at a coil temperature of 23°C.
3. The maximum voltage is the highest voltage that can be imposed on the relay coil.
Coil inductance Armature OFF
(H) (ref. value) Armature ON
Coil inductance Armature OFF
(H) (ref. value) Armature ON
Set Coil
Reset Coil
Omron 08 Cat 1-302 5/10/07 15:39 Page 190