Datasheet

119
Text
118
Text
Item Bifurcated contacts High-sensitivity
Number of poles 1 pole 1 pole 2 poles
Load Resistive load Inductive load Resistive load Inductive load Resistive load Inductive load
(cosϕ = 1) (cosϕ = 0.4; (cosϕ = 1) (cosϕ = 0.4; (cosϕ = 1) (cosϕ = 0.4;
L/R = 7 ms) L/R = 7 ms) L/R = 7 ms)
Rated Load 5 A at 250 VAC; 2 A at 250 VAC; 5 A at 250 VAC; 2 A at 250 VAC; 3 A at 250 VAC; 1 A at 250 VAC;
5 A at 30 VDC 3 A at 30 VDC 5 A at 30 VDC 3 A at 30 VDC 3 A at 30 VDC 1.5 A at 30 VDC
Rated carry current 5 A5 A3 A
Max. switching voltage 380 VAC, 125 VDC 380 VAC, 125 VDC 380 VAC, 125 VDC
Max. switching current 5 A5 A3 A
Max. switching power 1,250 VA, 500 VA, 1,250 VA, 500 VA, 750 VA, 250 VA,
150 W 90 W 150 W 90 W 90 W 45 W
Failure rate 1 mA at 5 VDC 100 mA at 5 VDC 10 mA at 5 VDC
(reference value)
Note: P level: λ
60
= 0.1 x 10
-6
/operation.
PCB/Flux Protection Relays
Item General-purpose, quick-connect terminal High-capacity
Number of poles 1 pole 2 poles 1 pole
Load Resistive load Inductive load Resistive load Inductive load Resistive load Inductive load
(cosϕ = 1) (cosϕ = 0.4; (cosϕ = 1) (cosϕ = 0.4; (cosϕ = 1) (cosϕ = 0.4;
L/R = 7 ms) L/R = 7 ms) L/R = 7 ms)
Rated Load 10 A at 250 VAC; 7.5 A at 250 5 A at 250 VAC; 2 A at 250 VAC; 16 A at 250 VAC; 8 A at 250 VAC;
10 A at 30 VDC VAC; 5 A at 30 VDC 3 A at 30 VDC 16 A at 30 VDC 8 A at 30 VDC
5 A at 30 VDC
Contact material AgSnIn
Rated carry current 10 A 5 A 16 A
Max. switching voltage 380 VAC, 125 VDC 380 VAC, 125 VDC 380 VAC, 125 VDC
Max. switching current 10 A 5 A 16 A
Max. switching power 2,500 VA, 1,875 VA, 1,250 VA, 500 VA, 4,000 VA, 2,000 VA,
300 W 150 W 150 W 90 W 480 W 240 W
Failure rate 100 mA at 5 VDC 10 mA at 5 VDC 100 mA at 5 VDC
(reference value)
Note: 1. P level: λ
60
= 0.1 x 10
-6
/operation.
Contact Ratings
PCB/Flux Protection, Plug-in, Quick-connect Terminal Relays
PCB Power Relay – G2R
PCB Power Relay – G2R
Power Relays
High-sensitivity Relays
Rated voltage 5 VDC 6 VDC 12 VDC 24 VDC 48 VDC
Rated current (50/60Hz) 71.4 mA 60 mA 30 mA 15 mA 7.5 mA
(see Note. 1)
Coil resistance (see Note. 1) 70 Ω 100 Ω 400 Ω 1,600 Ω 6,400 Ω
0.37 0.53 2.14 7.80 31.20
0.75 1.07 4.27 15.60 62.40
Must operate voltage 70% max. of rated voltage
Must release voltage 15% min. of rated voltage
Max. voltage 170% of rated voltage (at 23°C)
Power consumption Approx. 0.36 W
Note: 1. The rated current and coil resistance are measured at a coil temperature of 23°C with a tolerance of
+15%
/
–20%
(AC rated
current) or ±10% (DC coil resistance)
2. Operating characteristics are measured at a coil temperature of 23°C
3. Depending on the type of relay, some relays do not have coil specifications. Contact your Omron representative for more
details.
Coil inductance Armature OFF
(H) (ref. value) Armature ON
Double-winding Latching Relays
Rated voltage 5 VDC 6 VDC 12 VDC 24 VDC
Rated current (see note 1.) 167 mA 138 mA 70.6 mA 34.6 mA
Coil resistance (see note 1.) 30 Ω 43.5 Ω 170 Ω 694 Ω
0.073 0.104 0.42 1.74
0.146 0.208 0.83 3.43
Rated current 119 mA 100 mA 50 mA 25 mA
Coil resistance 42 Ω 60 Ω 240 Ω 960 Ω
0.003 0.005 0.018 0.079
0.006 0.009 0.036 0.148
Must set voltage 70% max. of rated voltage
Must reset voltage 70% max. of rated voltage
Max. voltage 140% of rated voltage (at 23°C)
Power consumption Set coil: Approx. 850 mW; Reset coil: Approx. 600 mW
Note: 1. The rated current and coil resistance are measured at a coil temperature of 23°C with a tolerance of ±10%.
2. Operating characteristics are measured at a coil temperature of 23°C.
Coil inductance Armature OFF
(H) (ref. value) Armature ON
Coil inductance Armature OFF
(H) (ref. value) Armature ON
Set Coil
Reset Coil
Omron 08 Cat 1-302 5/10/07 15:39 Page 118