Datasheet
1
MEMS Air Velocity Sensor – D6F-V03A1
Ordering Information
Item Term Ratings Unit
Power-supply voltage VCC 12 VDC
Output voltage V
OUT 3.0 VDC
Electrical Performance
Recommended operation condition and DC characteristic
Rating
Absolute maximum rating
Item Term Condition MIN TYP MAX Unit
Power-supply voltage VCC – 3.15 3.3 3.45 VDC
Operating temperature TOPR –-10–60°C
Maximum output V
OH Load resistance 10kR – – 2.7 VDC
voltage
Minimum output V
OL Load resistance 10kR 0 – – VDC
voltage
Model Case Applicable Gas Flow Range
D6F-V03A1 Thermoplastic resin Air* 0-3 m /sec
D6F-CABLE2
*Dry gas must not contain large particles, eg. dust, oil, mist.
Compact, intelligent sensors
featuring MEMS precision
technology for repeatable airflow
detection
■
RoHS / Lead-free and lead solder compatible
■
Precision uni-directional air velocity detection
■
Integral passive Dust Segregation
System (DSS)
■
Ultra compact size 24 (L) x 14 (W) x 8 (H) mm
Application Examples
• Cassette (ceiling / suspended), multi-modular air conditioners
• Duct connected heating and air conditioning systems
• Alternative for single point Pitot tube
• Alternative for thermal dispersion measurement
• Air & water cooled chillers, indoor packaged AC systems
• Window / split, multi-split residential AC coolers
• Air purifiers, dehumidifiers
• Fan assisted space heaters
• Air cooled, high power indoor lighting
• Mission critical PC, Workstation ventilation
• 19" rack / tray mounted PSU watchdog ventilation systems
MEMS D6F-V03A1 14/6/06 12:57 pm Page 1