Owner's manual

GENERAL
Line Voltage/Power: 90 to 240 Vac +/-10%, 50 to 400 Hz*;
110 to 375 Vdc, equivalent voltage; 4 W
* No CE compliance above 60 Hz
Low Voltage/Power Option:
12 to 36 Vdc or 24 Vac
**
+/-10%
; 3 W
External power source must meet Safety
Agency Approvals.
**Units can be powered safely with 24 Vac power
but, no Certification for CE are claimed.
External Fuse Required:
Time-Lag, IEC 127-3 recognized: 100 mA/250 V 400 mA/250 V
(Low Voltage/Power Option)
Time-Delay, UL 248-14 listed: 100 mA/250 V 400 mA/250 V
(Low Voltage/Power Option)
Environmental Conditions: 0 to 55°C (32 to 131°F), 90% RH non-condensing
Dimensions: 93H x 40W x 125mm D (3.64 x 1.55 x 4.93")
Software: The software packages available for the
Temperature Wireless System products are
iConnect (configuration software for the
Ethernet interface), iLog (Excel-based software
for automatic data logging), and Mail Notifier
(email alarm notification software).
INTERFACE SPECIFICATIONS
Ethernet: Standards Compliance IEEE 802.3 10Base-T
(RJ45)
Supported Protocols: TCP/IP, ARP, ICMP, DHCP, DNS, HTTP, and
Telnet
LED Indicators: Network Activity, Network Link, Diagnostics,
Receive & Power
Management: Device configuration and monitoring through
embedded Web Server
Embedded Web Server: Serves WEB pages (Java™ Applets)
containing real-time data and live updated
charts within definable time intervals.
WIRELESS COMMUNICATION
Standard: DSSS; IEEE 802.15.4
Frequency 2.4 GHz (2410 MHz), 12 Channels
Network Topology: Star Topology
64