- Omega Real-Time Clock Users' Guide

20
DISPLAY DESCRIPTION FACTORY

Sunday


Monday






Saturday
Friday
Thursday
Wednesday
Tuesday





TIME-OUT VALUE
 to 
ª
«


ª
«


TIMER STOP
ª
«


SETPOINT POWER-UP STATE
Determines the on/off state of the Setpoint output at power-up. Regardless of
output logic setting (normal or reverse).
 Deactivates the Setpoint output at power-up
 Activates the Setpoint output at power-up
 Restores the output to the state it was in prior to power-down
 

Timer stops when the Setpoint output activates () or deactivates ().
Select  if the output should not affect the Timer Run/Stop status.
Stopping the Timer as a result of this parameter does not constitute a 
condition (event) for the Setpoint On or Setpoint Off parameters.
This parameter only appears when the Setpoint is assigned () to the
Real-Time Clock Time display (). This parameter determines the days of
the week when the Setpoint output will activate.
Selecting  displays a sublist for choosing the days of the week. On all
days entered as  in the sublist, the output will activate. On all days entered
as , the output will not activate. The output activation is repetitive, and will
occur every week on the chosen day(s).
ª
«


This parameter only appears when the Setpoint is assigned () to the
Real-Time Clock Time display () and when the Setpoint Action ()
is programmed for On-Off Output mode (). In this mode, this parameter
determines the days of the week when the Setpoint output will deactivate.
Selecting  displays a sublist for choosing the days of the week. On all
days entered as  in the sublist, the output will deactivate. On all days entered
as , the output will not deactivate. The output deactivation is repetitive, and
will occur every week on the chosen day(s).
ª
«


The Time-Out Value only appears when the Setpoint Action () is
programmed for Timed Output mode (). In this mode, the Time-Out Value
is the Setpoint Output time duration, from activation to deactivation. This value
is always entered in minutes, seconds, and hundredths of seconds format. The
maximum Time-Out Value is 99 minutes 59.99 seconds.
 
ª
«


TIMER/COUNTER AUTO RESET
When the Setpoint output activates () or deactivates (), the meter
automatically resets the Setpoint Assignment display (). Select  if the
Setpoint output should not cause the assigned display to reset. Does not apply
to manual activations or deactivations by user input, function key, or serial
communications.
 
ª
«


OUTPUT RESET WITH DISPLAY RESET
When  is selected, the Setpoint output will reset when the Setpoint
Assignment display () resets. Select  if the Setpoint output should not
reset when the assigned display resets.
ª
«


SETPOINT ANNUNCIATOR
This parameter controls the illumination of the LED annunciator for the
corresponding Setpoint output () as follows:
   
 
 

Saturday


Friday


Thursday


Wednesday


Tuesday


Monday


Sunday

FACTORYDESCRIPTIONDISPLAY
Normal ()
Annunciator displayed when output is “on” (activated)
Reverse ()
Annunciator displayed when output is “off” (deactivated)
Flash ()
Annunciator and display flashes when output is “on” (activated)
Off ()
Annunciator disabled
Setpoint One-Shot Mode
If all days are set to
, the Setpoint will operate in “One-shot” mode. When
a One-shot setpoint is enabled (armed), the setpoint output will activate at the
set time and disable itself from activating again. To enable or re-enable a one-
shot alarm, go to the Setpoint value entry display and press the Up or Dn key
repeatedly while the AM/PM digit is selected (flashing). When the 2nd digit
decimal point is lit, the Setpoint is enabled. The Setpoint enable status is saved
at power-down. The enable state of the Setpoint is not affected or changed when
the Parameter List is exchanged.
The setpoint will turn off (de-activate) as programmed per the Setpoint
Action selected. If  mode is selected, program all the Daily Off days to
 to have the Setpoint turn off at the next Daily Off Occurrence. The One-
shot status can also be viewed or set from the Setpoint Off value entry display.
PTC901: DAILY OFF OCCURRENCE
PTC901: DAILY ON OCCURRENCE