User manual

DBK5, pg. 4
879895 DBK Option Cards and Modules
CAUTION
When using the SSH output, do not use an external voltage reference for DAC1.
Applying an external voltage reference for DAC1, when using the SSH output, will result
in equipment damage due to a conflict on P1, pin #26.
2. Place the JP2 jumper in the SSH position (see above CAUTION).
3. For DaqBook/100, DaqBook/112 and DaqBook/120 only, place the JP4 jumper in single-ended
mode.
DaqBook/2000 Series & DaqBoard/2000 Series
No jumper configurations are required for these /2000 series devices.
Software Setup
Reference Notes:
o DaqView users - Refer to the DBK Setup section in the DaqView document.
o LogView users - Not Applicable.
DBK5 – Specifications
Name/Function: 4-Channel 4-20 mA Current Output Card
Connectors: DB37 male, mates with P1. Screw terminals for signal output.
Accuracy/Linearity: 0.1% FS
Resolution: 4 µA / LSB, monotonic
Hysteresis: 0.02% FS
Regulation: 0.05% FS
Compliance: R
LOOP
= (V
SUPPLY
- 6) / 0.020 max
Isolation: 500 V