BVLS Series Limit Switch for BVP70, BVPS70, BVP80 & BVPS80 Series Actuated Ball Valves
MATERIALS OF CONSTRUCTION BODY / COVER: Aluminium with Teflon Imprenated Hard Anodized (PolyLube) Surfaces PROBES: 316 Stainless Steel SEALS - COVER, PROBES: Buna N RATINGS / SPECIFICATIONS TEMPERATURE: 10 F to 180 F CONDUIT CONNECTION: 1/2” NPT ELECTRICAL RATING: 10 amp. 250VAC maximum; 1/2 amp. 125VDC; 1/4 amp. 250VDC; 5 amp. 125VAC lamp load. Note: each pole must be the same polarity to utilize these ratings. MICROSWITCHES: Mechanical S.P.D.T.
Attachment of Limit Switch / NAMUR Mounting Pad 1. Remove the position indicator from atop the actuator and secure the NAMUR 30 Shaft Coupling to the actuator Shaft Extension with the #6-32 Set Screw using a medium strength (nonpermanent) thread locker (not included in mounting kit). 2. Place the Limit Switch / NAMUR Mounting Pad on top of the actuator.
6
M-4153/0405