Cut Sheet

1.3 SUBMITTALS
A. General: Submit in accordance with Section 01 33 00.
B. Product Data:
1. Submit manufacturer’s descriptive literature and product specifications
for each product.
2. Manufacturer’s installation literature and training guide.
3. Manufacturer’s product drawings, when applicable.
1.4 QUALITY ASSURANCE
A. Manufacturer Qualifications: Products shall be free of defects in material
and workmanship.
B. Installer Qualifications: Installer shall be trained and certified based on the
acceptable manufacturers listed requirements.
PART 2 – PRODUCTS
2.1 GENERAL
A. Furnish PVC coated ERMC of size as indicated. If not indicated, the
smallest trade size shall be 3/4-inch. The PVC coated ERMC system
shall include necessary PVC coated fittings, boxes and covers to form a
complete encapsulated system.
2.2 MANUFACTURERS
A. Acceptable Manufacturers: Thomas & Betts Corporation; 8155 T & B
Blvd., Memphis, TN 38125. Tel: 901-252-5000. Web: www.tnb.com
B. Substitutions: Not permitted
C. Requests for substitutions will be considered in accordance with
provisions of Section 01 25 00.
2.3 MATERIALS / COMPONENTS
A. PVC COATED RIGID STEEL CONDUIT:
The PVC coated rigid steel conduit shall be hot dip galvanized inside and
out with hot dipped galvanized threads. The interior galvanizing shall be
listed per UL 6. The exterior galvanizing shall be listed per UL 6 as
primary corrosion protection. Thread protectors shall be used on the
exposed threads of the PVC coated conduit. PVC coated ERMC- steel
conduit shall comply with UL 6, ANSI C80.1, and NEMA RN-1 standards
without exception.
The PVC coating, in compliance with NEMA RN-1, shall be nominal 40
THOMAS & BETTS GUIDE SPECIFICATIONS 26 05 33 CONDUIT SYSTEMS FOR
CORROSIVE ENVIRONMENTS