Datasheet
Chapter 3 Modes of Operation
MC9S08JM60 Series Data Sheet, Rev. 3
Freescale Semiconductor 37
3.6 Stop Modes
One of two stop modes is entered upon execution of a STOP instruction when STOPE in SOPT1 is set. In 
any stop mode, the bus and CPU clocks are halted. The MCG module can be configured to leave the 
reference clocks running. See Chapter 12, “Multi-Purpose Clock Generator (S08MCGV1),” for more 
information.
Table 3-1 shows all of the control bits that affect stop mode selection and the mode selected under various 
conditions. The selected mode is entered following the execution of a STOP instruction.
3.6.1 Stop3 Mode
Stop3 mode is entered by executing a STOP instruction under the conditions as shown in Table 3-1. The 
states of all of the internal registers and logic, RAM contents, and I/O pin states are maintained.
Stop3 can be exited by asserting RESET, or by an interrupt from one of the following sources: the real-time 
clock (RTC) interrupt, the USB resume interrupt, LVD, ADC, IRQ, KBI, SCI, or the ACMP.
If stop3 is exited by means of the RESET
 pin, then the MCU is reset and operation will resume after taking 
the reset vector. Exit by means of one of the internal interrupt sources results in the MCU taking the 
appropriate interrupt vector.
3.6.1.1 LVD Enabled in Stop Mode
The LVD system is capable of generating either an interrupt or a reset when the supply voltage drops below 
the LVD voltage. If the LVD is enabled in stop (LVDE and LVDSE bits in SPMSC1 both set) at the time 
the CPU executes a STOP instruction, then the voltage regulator remains active during stop mode. If the 
user attempts to enter stop2 with the LVD enabled for stop, the MCU will enter stop3 instead.
For the ADC to operate, the LVD must be left enabled when entering stop3. For the ACMP to operate when 
ACGBS in ACMPSC is set, the LVD must be left enabled when entering stop3.
For the XOSC to operate with an external reference when RANGE in MCGC2 is set, the LVD must be left 
enabled when entering stop3.
Table 3-1. Stop Mode Selection
STOPE ENBDM 
1
1
ENBDM is located in the BDCSCR which is only accessible through BDC commands, see Section 18.4.1.1, 
“BDC Status and Control Register (BDCSCR).”
LVD E LVD SE PP DC St op  Mo de
0 x x x Stop modes disabled; illegal opcode reset if STOP 
instruction executed
1 1 x x Stop3 with BDM enabled 
2
2
When in stop3 mode with BDM enabled, The S
IDD
 will be near R
IDD
 levels because internal clocks are 
enabled.
1 0 Both bits must be 1 x Stop3 with voltage regulator active
1 0 Either bit a 0 0 Stop3
1 0 Either bit a 0 1 Stop2










