Installation Guide

6 | nVent.com/RAYCHEM
The following limiting temperatures for the end seals, splices and power
connections shall not be exceeded:
+110°C for the S-20 and E-20
+260°C for the E-40 and S-40
+150°C for the C-150-E, S-150 and E-150
+151°C for the E-100, E-100-L and JBS-100
+155°C for the JBM-100 and T-100
+110°C for the C25-21 and C25-100
+180°C for the C25-100-METAL/C3/4-100-METAL
The E-100, E-100-L, JBM-100, JBM-100-L, JBS-100, JBS-100-L and
T-100 have limiting temperatures based on an internal component in
these accessories. When located on a pipe or other work piece surface,
a maximum pipe temperature of 250°C will not cause the limiting
temperatures of 151°C or 155°C to be exceeded
The end seals, splices and power connections have the following
associated ambient temperatures:
–60°C to +56°C for the E-20 and S-20
–60°C to +56°C for the E-40 and S-40
–55°C to +56°C for the T-100, JBM-100, JBS-100, JBU-100 and E-100
–40°C to +56°C for the JBS-100-L, JBM-100-L, and JBU-100-L
–55°C to +55°C for the C-150-E, S-150 and E-150
–40°C to +40°C for the E-100-L
–55°C to +110°C for the C25-21 and C25-100
–60°C to +180°C for the C25-100-METAL / C3/4-100-METAL /
C25-100-METAL-NP / C3/4-100-METAL-NP / C25-100-METAL-SS
The assembly of glands, splices and end terminations
shall be carried out in accordance with the manufacturing
instructions.
The heating element supply circuit must include an electrical
protection device in conformity with Clause 4.4 of IEC
60079-30-1. For the JBM-100-L, JBU-100-L and JBS-100-L
this shall be limited to 20A maximum when used at ambient
temperatures above 40°C.
The minimum installation temperature of the heating
cables is –60°C. The minimum bending radii at specific
temperatures are shown on the next pages of this document.
The supply to the heating unit must be terminated in a
suitably certified terminal enclosure.
At ambient temperatures above 40°C temperature resistant
power cable suitable for temperatures above 90°C and metal
glands must be used.
The minimum installation temperature for E-20 and S-20
is –20°C.
The installer is to carry out a dielectric strength test on
Ex equipment in which the C25-21, C25-100 and C25-100-
Metal / C3/4-100-Metal / C25-100-Metal-NP / C3/4-100-
Metal-NP / C25-100-Metal-SS connection kit is fitted. No
dielectric breakdown shall occur. (Alternatively, an insulation
resistance test may be undertaken in accordance with
IEC 60079-30-2)