Installation Guide
nVent.com/RAYCHEM
|
5
HTV IECxPTB21.0007X Ex 60079-30-1 eb IIC T* Gb
Ex 60079-30-1 tb IIIC T**°C Db
or
Ex 60079-30-1 eb mb IIC T* Gb
Ex 60079-30-1 mb tb IIIC T**°C Db
Tmin -60°C (* ** see schedule)
VPL IECEx BAS 20.0008X “Ex 60079-30-1 eb IIC T* Gb
Ex 60079-30-1 tb IIIC T**°C Db
or
Ex 60079-30-1 eb mb IIC T* Gb
Ex 60079-30-1 mb tb IIIC T**°C Db
Tmin –60°C (* ** see schedule)”
Product
name
in SAP Certificate No Code
BTV
CABLE
ТС RU C-BE.
МЮ62.В.00054/18
1Ex e IIC T6 Gb X 1Ex e mb II C T6 Gb X
Ex tb IIIC T80°C Db X Ex tb mb IIIC T80°C Db X
Ta –60°C…+56°C IP66
QTVR
CABLE
ТС RU C-BE.
МЮ62.В.00054/18
1Ex e IIC T4 Gb X 1Ex e mb IIC T4 Gb X
Ex tb IIIC T130°C Db X Ex tb mb IIIC T130°C Db X
Ta –60°C…+56°C IP66
XTV
CABLE
ТС RU C-BE.
МЮ62.В.00054/18
1Ex e IIC T* Gb X 1Ex e mb IIC T* Gb X
Ex tb IIIC T* Db X Ex tb mb IIIC T* Db X
Ta –60°C…+56°C IP66
KTV
CABLE
ТС RU C-BE.
МЮ62.В.00054/18
1Ex e IIC 226°C (T2) Gb X 1Ex e mb IIC 226°C (T2)
Gb X
Ex tb IIIC T226°C Db X Ex tb mb IIIC T226°C Db X
Ta –60°C…+56°C IP66
HTV
CABLE
EAЭС RU C-BE.
AЖ58.B.01728/21
1 Ex e mb 60079-30-1 IIC 180°C (T3)...215°C (T2) Gb X
Ex tb 60079-30-1 IIIC 180°C ... 215°C Db X
VPL
CABLE
ТС RU C-BE.
МЮ62.В.00054/18
1Ex e IIC T* Gb X 1Ex e mb IIC T* Gb X
Ex tb IIIC T* Db X Ex tb mb IIIC T* Db X
Ta –60°C…+56°C IP66
BSA cables are EAC certied to TR CU 004/2011
Warning
As with any electrical equipment or wiring installation operating
at line voltages, heating cable and component damage or
incorrect installation that allows the penetration of moisture
or contamination can lead to electrical tracking, arcing and
potential fire hazard.
Do not connect heating cable conductors together or this will
result in a short circuit.
Any unconnected heating cable end must be sealed with a
nVent approved end seal.
To prevent fire or explosion in hazardous areas, verify that the
maximum sheath temperature of the heating cable is below the
auto-ignition temperature of the gases in the area. For further
information, see design documentation.
The purchaser should make the manufacturer aware of any
external effects or aggressive substances that the equipment
may be exposed to.