Installation Guide

36 | nVent.com/RAYCHEM
Troubleshooting guide
A Symptom: Overcurrent protection trips or blows
Probable Causes
1 Electrical fault at
a damaged heating cable
b faulty splices or tees
c end seal
d  connection
2 Circuit oversized
3 Start-up below design temperature
4 Defective electrical protection
B  Symptom: RCD trips
Probable Causes
1 Earth fault at:
a damaged heating cable
b faulty splices or tees
c end seal
d connection
2 Excessive moisture in:
a junction boxes
b splices and tees
c end seals
3 High leakage currents due to a combination
of excessive lengths of power cable and heating cable.
4 Mains borne disturbances
5 Defective RCD