Installation Guide

nVent.com/RAYCHEM
|
31
9 OPERATION, MAINTENANCE AND
PIPE REPAIRS
Caution: consult the heat tracing system documentation prior to
maintenance/repair/modification.
9.1 Heating cable operation
Temperature exposure must not exceed that specified in
nVent product literature. Exceeding those limitations will
shorten the service life and may permanently damage the
heating cable.
Pipe insulation must be complete and dry to maintain the
correct temperature.
9.2 Inspection and maintenance
Visual inspection: Exposed heating cable and pipe insulation
should be checked periodically to make sure that no physical
damage has occurred.
Upon completion of maintenance/repair/modification, the
insulation resistance of the heating cable shall be measured
and recorded and shall not be less than 1000 Megaohms
Meggering: The system should be meggered regularly. When
meggering the insulation resistance from the main supply
panel, it is recommended that the test is performed between
L/N (together) and PE. Freeze protection systems should be
meggered before the winter months each year (see section
8). Temperature maintenance systems should be tested at
least twice a year. Function testing of electrical protection
and temperature control systems should be carried out at
regular intervals.
The Periodic Inspection Record on the following pages
should be filled out during maintenance of each circuit in
your system.
9.3 Piping systems repair and maintenance
After maintenance/repair/modification, test the operation of
the earth-fault device of each affected circuit or equivalent.
Isolate heating cable circuit.
Protect the heating cable from mechanical or thermal
damage during pipe repair work.
Check heating cable installation after pipe repairs and
restore thermal insulation following the recommendations
in Section 6. Check correct functioning of electrical
protection systems.