Installation Guide

26 | nVent.com/RAYCHEM
6 THERMAL INSULATION AND MARKING
6.1 Pre-insulation checks
Visually inspect the heating cable and components
for correct installation and damage. (See Section 10 if
damaged.)
Insulation resistance (Megger) testing (as per Section 8) is
recommended prior to covering the pipe with thermal
insulation.
6.2 Insulation installation hints
Correct temperature maintenance requires properly installed
and dry thermal insulation.
Thermally insulate and weatherproof to design specification.
Check insulation type and thickness against the design
specification.
To minimize potential heating cable damage, insulate as
soon as possible after tracing.
Check that all pipework, including fittings, wall penetrations
and other areas, have been completely insulated.
Ensure that heating cable is not damaged during installation
of cladding for example by drills, self tapping screws and
sharp edges of cladding.
Check that all insulation entry kits are fitted correctly
and sealed.
Ensure that all places where valve stems, support brackets,
thermostat capillaries, etc exit the cladding are sealed.