Installation Guide

nVent.com/RAYCHEM
|
15
Refer to design specification for spiral pitch
Mark the pipe at the spiral pitch or use a simple length gauge
Fix the heating cable as installation progresses
Thermally insulate and weatherproof to specification
3.5 Cutting the heating cable
Cut the heating cable to length after it is attached to the
pipe. Before cutting it, confirm the tracing allowance as per
Sections 3.3 and 3.6.
nVent RAYCHEM heating cable can be cut to length without
affecting the heat output per metre.
3.6 Typical installation details
Typical installation details for fixing heating cable to pipe
fittings are shown hereafter.
General notes:
Trace pipe fittings as shown to allow easy maintenance.
Consult the design specification or nVent product literature
or TraceCalc software for the tracing requirements for
fittings and supports.
Follow the recommendations for cutting and stripping
heating cables; they are included in the component
installation instructions.
3.6.1 Valve
Figure 3
Theheatingcablecongurationwill
vary for different valve shapes and
heating cable lengths.
Heating cable
Glass tape
Valve body
Pipe
Refer to design specification for additional heating
cable length.
Fix with self-adhesive glass cloth tape.
Thermally insulate and weatherproof to specification
(including valve stem).