Cut Sheet

APPROVALS
Class I, Div. 2, Groups A, B, C, D
Class II, Div. 1 and 2, Groups E, F, G
Class III
09-IEx-0004X
(3)
Ex e IIC T* Gb
CLI, ZN1, AEx e II T
(2)
Ex e II T
(2)
Hazardous Locations
(1)
(1)
Except VPL
(2)
For T-rating, see heating cable or design
documentation
(3)
Except KTV
-ws -ws
ll 2G ll 2D
Ex e II
Ex tD A21 IP66
PTB 09 ATEX 1043U
IECEx PTB 09.0023U
DIMENSIONS NOMINAL
4.7 in
(120 mm)
3.6 in
(90 mm)
4.7 in
(120 mm)
4.7 in
(120 mm)
PRODUCT SPECIFICATIONS
Heating cable capability BTV-CR, BTV-CT, QTVR-CT, XTV-CT, KTV-CT, and VPL-CT
Ingress protection NEMA 4X / IP66 / IP67
Minimum installation temperature –40°F (–40°C)
Minimum ambient temperature –75°F (–60°C)
Maximum ambient temperature 132°F (56°C)
Maximum pipe temperature 500°F (260°C)
Maximum operating voltage 480 Vac
Maximum circuit breaker rating 50 A for FM, CSA; 40 A for PTB
MATERIALS
Enclosure Electrostatic charge-resistant glass-filled engineered polymer, black
Lid screws Stainless steel
Lid gasket Silicone rubber
ORDERING DETAILS
Catalog number T-100
Part number 447379-000
Weight 2.5 lb (1.2 kg)
Crimp tool T-100-CT (not included in kit; equivalent to Panduit CT-1570)
PN 954799-000
Spare crimps and insulating tubes T-100-CRIMP-KIT PN 577853-000
T100
THERMAL MANAGEMENT SOLUTIONS
EN-RaychemT100-DS-H53874 09/13
2 / 3