POSITIONING THE SENSOR
Position the RTD sensor in the lower quadrant of the pipe as shown
in the diagram. Place the RTD sensor at least 3 feet (1 m) from
pipe supports, valves, or other heat sinks. Tape the RTD firmly to
thepipewithAT-180aluminumtape,makingsurethereisnoair
space between the RTD and the pipe. Do not use the same piece of
AT-180 tape to overlap the RTD and heat-trace cable.
90
Heating cable
Control sensor
AT-180 tape
AT-180 tape
Heating cable
Control
thermostat bulb
Double traced
Single traced
INSTALLATION WITH HEATING CABLE
Electrical Wiring Guidelines:
Mostelectricalcodes(suchasNEC725.15)permitClass1circuits
to occupy the same cable, enclosure, or raceway without regard
towhethertheindividualcircuitsarealternatingcurrentordirect
current,providingallconductorsareinsulatedforthemaximum
voltageofanyconductorsinthecable,enclosureorraceway.
Additional Materials Required
• JBS-100-Aorotherpowerconnectionkit
• Pipestraps
Conduit
drain
JBS-100-A
Sensor
Splice box
(not provided -- must
be approved for area
classification)
To controller
RTD DIRECT CONNECTION TO CONTROLLER
(Distance from sensor bulb to controller must be less than 10 feet)
The RTD3CS and RTD10CS can be terminated directly at the con-
troller using the supplied ½ inch NPT fitting. In this configuration,
no additional extension wire is required.
Sensor
Stainless steel
flexible armor
(3 ft or less for RTD3CS and
10 ft or less for RTD10CS)
DigiTrace controller
RTD DIRECT CONNECTION TO CONTROLLER
(Distance from sensor bulb to controller greater than 3 feet for the
RTD3CS and 10 feet for the RTD10CS)
Sensor
Splice box
(not provided - must be
approved for area classification)
To controller
Conduit
drain
RTD3CS AND RTD10CS WIRING
Connect the wires as shown.
Note: GroundRTDextensionwireshieldatoneendonly,
preferably at DigiTrace electronics end.
Red (Source)
White
Red
Red
Red (Compensate)
Field Wiring (if required)
White (Common return)