DESCRIPTION
The RTD3CS and RTD10CS are three-wire platinum RTD
(resistance temperature detectors) typically used with monitoring
and control systems, such as our DigiTrace 910 controller, when
accurate temperature control is required.
The RTD3CS and RTD10CS can be installed directly to the
controller using the supplied ½ inch conduit fitting or to an RTD
junction box where RTD extension wire is used.
TOOLS REQUIRED
• 3.5-mmflat-bladescrewdriver
ADDITIONAL MATERIALS REQUIRED
• AT-180aluminumtape
KIT CONTENTS
Qty Description
1 RTD temperature sensor
This component is an electrical device. It must be installed
correctly to ensure proper operation and to prevent shock or
fire. Read these important warnings and carefully follow all the
installation instructions. Component approvals and performance
are based on the use of s pecified parts only. Do not use substitute
parts or vinyl electrical tape to make connections.
WARNING:
Extension Wires
Wire size
(each of 3)
20AWG,strandedtinnedcopper
Wire insulation
rating
300volts
Length RTD3CS: 3 ft (.3 m) flexible armor,
18in(457mm)leadwire
RTD10CS: 10 feet (3 m) flexible armor,
18in(457mm)leadwire
Outer shield Stainless steel flexible armor
Maximum exposure
temperature
400°F(204°C)
Conduit bushing ½ in NPT
APPROVALS
Approvalsassociatedwithcontroldevice,howevernottobeused
inDiv.1locations.
SPECIFICATIONS
Sensor
Housing 316 stainless steel
Dimensions 3in(76mm)length3/16in(8mm)diameter
Sensing area in(38mm)
Accuracy ±1°F(0.5°C)at32°F(0°C)
Range –76°Fto400°F(–60°Cto204°C)
Resistance 100ohmsat0°Cα=0.00385ohms/ohm/°C